Page 83 - MCCB-XT5
P. 83

ABB | SACE Tmax XT

       12 - Performance table



                     General notes:  •  The performance values given in the next table are valid with  100 ms trip time, temperature
                                       and signals within the operating limits; failure to comply with these limitations could lead to an
                                       increase in the tolerances.
                                     •  Ekip Touch sends the TRIP command if the signal read exceeds the threshold for longer than the
                                       set time (or the time resulting from the calculation formula)
                                     •  With an inverse time-delay trip curve, the calculation refers to a signal with a constant value
                                       throughout the timing: variation of the alarm signal causes a different trip time
                                     •  The additional notes are given after all the tables


               Standard Protections  Protection                       Trip threshold
                                     [ANSI code]  Trip time t  t  (1)  tolerance  (3)   Trip time tolerance  (3)




                                                  (with curve t = k / I )  Activation for If   with If ≤ 6 In: ± 10 % / with If > 6
                                                                  2
                                     L [49]                           within range: (1.05 to   In: ± 20 %
                                                                      1.2) x I1
                                                  (with curves 60255-151)
                                                  t  = t2 ( with curve t =              The best between ± 10% and 40
                                                    t
                                                  k )                                   ms
                                     S [50TD / 51]                    with If ≤ 6 In: ± 7 % /
                                                                      with If > 6 In: ± 10 %  with If ≤ 6 In: ± 15 % / with If > 6
                                                                                        In: ± 20 %
                                                  (with curve t = k / I )
                                                                  2
                                                                      with If ≤ 6 In: ± 7 % /  The best between ± 10% and 40
                                     S2 [50TD]    t  = t5
                                                    t                 with If > 6 In: ± 10 %  ms
                                     I [50]       t  ≤ 30 ms          ± 10 %            --
                                                    t
                                                  t  = t4 ( with curve t =              The best between ± 10% and 40
                                                    t
                                                  k )                                   ms  (2)
                                     G [50N TD /                      ± 7 %
                                     51N]
                                                                                        ± 15 %
                                                                  2
                                                  (with curve t = k / I )
                                     MCR          t  ≤ 30 ms          ± 10 %            --
                                                    t
                                     2I [50]       (10)               ± 10 %            --
                                                                                        with t6 ≥ 5 s: ± 100 ms / with t6 <
                                     IU [46]      t  = t6             ± 10 %            5 s the best between ± 10 % and
                                                    t
                                                                                        ± 40 ms

                                    Startup
                                     Protection   Trip time t          Trip threshold   Trip time tolerance
                                     [ANSI code]            t          tolerance  (3)
                                                                       with If ≤ 6 In: ± 7
                                     S StartUp    t  = t2 startup      % / with If > 6 In:   The best between ± 10% and 40
                                                   t                                    ms
                                                                       ± 10 %
                                     I StartUp    t  ≤ 30 ms           ± 10 %           --
                                                   t
                                                                                        The best between ± 10% and 40
                                     G StartUp    t  = t4 startup      ± 7 %
                                                   t                                    ms
                                                                       with If ≤ 6 In: ± 7   The best between ± 10% and 40
                                     S2 StartUp   t  = t5 startup      % / with If > 6 In:
                                                   t                                    ms
                                                                       ± 10 %











       81 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                                Protections | 12 - Performance table