HVI Lightning Protection
                                                                                                                      HVI Lightning   Protection







                      HVI light Conductor                          Separation distance          s s
                                                                     s ≤ 45 cm "air"
                         DEHNcon-H                               s ≤ 90 cm "solid material"  < 75 cm
                                                                                             ≤ 45 cm


                    Technical data                            HVI light Conductor / DEHNcon-H
                    Outer diameter / colour                   20 mm / dark grey
                    Equivalent separation distance (air)      ≤ 45 cm
                    Equivalent separation distance (solid material)  ≤ 90 cm
                    Operating temperature                     -30 °C ... +70 °C
                    Tested with limp (10/350 µs) based on EN 62561-1  150 kA
                    For use in class of LPS in case of a single down conductor without   II, III, IV
                    current distribution (kc = 1)
                    Installation in Ex zone 1 and 21          not allowed
                    Maximum permissible conductor length LPL II (at kc = 1)  7.5 m
                    Maximum permissible conductor length LPL III / IV (at kc = 1)  11.25 m







                        HVI Conductor                               Separation distance         s s
                      HVI long Conductor                              s ≤ 75 cm "air"
                                                                                             ≤ 75 cm
                         DEHNcon-H                               s ≤ 150 cm "solid material"  < 75 cm


                    Technical data                            HVI Conductor / HVI long Conductor / DEHNcon-H
                    Outer diameter / colour                   20 mm / black or 23 mm / grey
                    Equivalent separation distance (air)      ≤ 75 cm
                    Equivalent separation distance (solid material)  ≤ 150 cm
                    Operating temperature                     -30 °C ... +70 °C
                    Tested with limp (10/350 µs) based on EN 62561-1  150 kA
                    For use in class of LPS in case of a single down conductor without   II, III, IV
                    current distribution (kc = 1)
                    Installation in Ex zone 1 and 21          allowed
                    Maximum permissible conductor length LPL II (at kc = 1)  12.5 m
                    Maximum permissible conductor length LPL III / IV (at kc = 1)  18.75 m








                     HVI power Conductor                            Separation distance         s s
                        HVI power long                                s ≤ 90 cm “air“
                                                                                             ≤ 90 cm
                          Conductor                              s ≤ 180 cm “solid material“  < 75 cm


                    Technical data                            HVI power Conductor / HVI power long Conductor
                    Outer diameter / colour                   27 mm / black
                    Equivalent separation distance (air)      ≤ 90 cm
                    Equivalent separation distance (solid material)  ≤ 180 cm
                    Operating temperature                     -50 °C ... +70 °C
                    Tested with limp (10/350 µs) based on EN 62561-1  200 kA
                    For use in class of LPS in case of a single down conductor without
                    current distribution (kc = 1)             I, II, III, IV
                    Installation in Ex zone 1 and 21          allowed
                    Maximum permissible conductor length LPL I (at kc = 1)  11.25 m
                    Maximum permissible conductor length LPL II (at kc = 1)  15.0 m
                    Maximum permissible conductor length LPL III / IV (at kc = 1)  22.5 m