HVI light Conductor  HVI light Conductor                                                            s s                                                                                                                                  HVI light Conductor






                                                                                                     ≤ 45 cm
                                                                                                     < 75 cm






















        The HVI light Conductor supplements the tried and tested HVI Conductor.   building along which partial lightning currents can flow and disturb or
        It enriches the design possibilities in lightning protection as it has been   even  destroy  the  sensitive  electric / electronic  equipment. The  isolated
        specially designed for low, large-scale buildings where the separation   air-termination system prevents this transfer of partial lightning currents
        distance cannot be maintained with conventional lightning protection   into the building. The HVI light Conductor is the right system for main-
        systems.                                             taining the separation distance on flat roofs. The high-voltage-resistant,
                                                             insulated HVI light Conductor prevents uncontrolled flashover to metal
        A significant advantage of the HVI light Conductor is that it is easy and   or electric components underneath the roofing.
        quick to install.
                                                             The HVI light Conductor is available on a 100 m disposable reel (diameter
        A sealing end which is connected to the functional equipotential bonding   approx. 800 mm, width approx. 485 mm) or on a 500 m disposable reel
        system of the building is not required. Instead, the conductor is connect-  (diameter approx. 1 m, width approx. 670 mm) for the installer to cut to
        ed at a defined coupling point to the supporting tube in the tripod. This   length on site or is already cut to length (6 - 70 m).
        does not have to be connected to the functional equipotential bonding
        system.                                              •  high-voltage-resistant, insulated HVI light Conductor for maintaining
                                                               the separation distance to electrically conductive parts according to
        Nowadays,  the  roof  area  of  buildings  is  often  used  as  an  installation   IEC 62305-3
        level  for  pipes,  electric  and  information  technical  systems  or  photo-  •  equivalent separation distance s ≤ 0.45 m (in air) or
        voltaic installations regardless of the potential risk of lightning strikes.   s ≤ 0.90 m (solid material)
        All of these systems have conductive connections to the interior of the



        Technical data                                       HVI light Conductor      HVI light Conductor
                                                             (on a reel)              (cut to length)
        Structure                                            solid                    solid
        Cross section of the inner conductor (Cu)            19 mm 2                  19 mm 2
        Colour of conductor                                  dark grey                dark grey
        Outer diameter                                       20 mm                    20 mm
        Equivalent separation distance (air)                 ≤ 45 cm                  ≤ 45 cm
        Equivalent separation distance (solid material)      ≤ 90 cm                  ≤ 90 cm
        Minimum bending radius (OD = outer diameter)         10 x OD, min. 200 mm     10 x OD, min. 200 mm
        Operating temperature                                -30 °C ... +70 °C        -30 °C ... +70 °C
        Installation temperature                             -5 °C ... +40 °C         -5 °C ... +40 °C
        Tensile strength                                     950 N                    950 N
        UV / weather-resistant                               yes                      yes
        Tested with limp (10/350 µs) based on EN 62561-1     150 kA                   150 kA
        For use in class of LPS in case of a single down conductor without
        current distribution (kc = 1)                        II, III, IV              II, III, IV
        Installation in Ex zone 1 and 21                     not allowed              not allowed
        Minimum order quantity                               100 m                    ≥ 6 m
        Max. order length                                    —                          70 m
        Cable weight / 100 m                                 ~ 40 kg                  —