HVI light Conductor


                          5  Adjustment Range, Separation Distance s ≤ 45 cm
                         Connection of the HVI light Conductor to an existing lightning protection system. The equivalent separation distance s at the connection point
                         of the HVI light Conductor is ≤ 45 cm (in air).
                         In the connection area an adjustment range around the HVI light Conductor has to be provided. No electrical, conductive or earthed parts
    HVI   light Conductor  may be installed in this area. This is necessary in order to couple the lightning current safely into the conductor. An equipotential bonding
                         connection is not necessary.




                                                                                             120 cm
                                                                                 l ≥ 45 cm
                                                                                                            1




                                                                                              2
                                                                                  insulating  clearance    = 91 cm  r ≥ 45 cm






                                                                             4       3
                                                                               5






                         Accessories for the Adjustment Range, Separation Distance s ≤ 45 cm


                         Connection element for HVI light Conductor
                         Connection element for sealing and connecting the HVI light Conductor to other parts of the external lightning protection system or earth-ter-
                         mination system. Heat-shrinkable sleeve included.
         1                Part No.                    819 299
                          PU                          1 pc(s)


                         Spacers for HVI light Conductor
         2               Spacer for implementing the adjustment range (length 1200 mm) without additional connection to the equipotential bonding.
                         The spacer is installed, e.g. in a concrete block with fixing wedge (17 kg) (Part No. 102 340).
                          Part No.                    106 812
                          PU                          1 pc(s)


         3               Concrete base
                         With fixing wedge and adapted base plate, stackable.
                          Part No.                    102 340
                          PU                          54 pc(s)



                         Roof conductor holder for flat roofs
         4               For fixing round conductors and strips on flat roofs with one conductor support type FB.
                          Part No.                    253 015
                          PU                          10 pc(s)


                         Adapter for installing the HVI light Conductor / HVI Conductor on flat roofs
                         To be snapped on roof conductor holder type FB (Part No. 253 015).
         5                Part No.                    253 026
                          PU                          50 pc(s)