P. 157

HVI light Conductor

            5  Variable Adjustment Range, Connection to "Isolated Ring Conductor"
           If several installation parts require protection, it is advisable not to route the HVI light Conductor of each air-termination system individually
           to the earth-termination system. The HVI light Conductors from the air-termination system can be connected to an "isolated ring conductor".
           From this "isolated ring conductor" several down conductors, HVI light Conductors, can then be led to the earth-termination system. The
                                                                                                                      HVI   light Conductor
           "isolated ring conductor" must be installed, e.g. on the roof, on spacers and concrete bases, taking the calculated separation distance "s"
           into account.



                                                                             2  l = sair x 2
                                                                               35 - max. 90 cm





                                                                                             5


                                                                        sair


                                                                        l ≥ sair    1



                                                                            3, 4






           Accessories for the Variable Adjustment Range, Connection to "Isolated Ring Conductor"


           Spacer with EB element for HVI light Conductor (length of variable adjustment range 350-900 mm)
           Spacer for implementing the variable adjustment range of the HVI light Conductor.                   1
           With MV clamp for connection to the equipotential bonding (Rd 16 mm / Rd 8-10 mm).      Eurocode
           Concrete base (Part No. 102 010, weight 17 kg) and base plate (Part No. 102 050) must be ordered separately.
           Part No.                    105 460
           PU                          1 pc(s)


           DEHNiso spacers with MMV clamp
           For crossing points, when installed in a concrete base (Part No. 102 075), fixed conductor routing.
                                                                                                               2
           Part No.                    106 150                                                     Eurocode
           PU                          1 pc(s)


           Concrete base                                                                                       3
           With fixing wedge, stackable, for erecting tripods and air-termination rods Ø16 mm, chamfered or tapered, DEHNiso spacer Ø16 mm or
           conductor holder (Part No. 253 279).
           Part No.                    102 010
           PU                          54 pc(s)


                                                                                                               4
           Base plate
           To protect the roof sheeting under the concrete base. For concrete bases (Part Nos. 102 010, 102 002).
           Part No.                    102 050
           PU                          1 pc(s)


           MV clamp
           With hexagon screw, spring washer and thread in the base part. Lightning current carrying capability 200 kA (10/350 μs).
                                                                                                               5
           Part No.                    390 209
           PU                          1 pc(s)