Page 51 - dehn-catalogue-safety-equipment_0
P. 51

DEHNcap/P Voltage Indicator  DEHNcap/A Voltage Indicator DEHNcap/IT Interface Test Unit  DEHNcap/PC Phase Comparator  DEHNcap HR LRM Test Set  DEHNcap Test Adapter
           3. Verify that the Installation is dead – DEHNcap Voltage Detecting System

           Electrical and mechanical interface requirements for pluggable HR, LR and LRM voltage detecting systems
                                                       HR                     LR                    LRM
           System description
                                                   high resistance        low resistance     low resistance, modified
           Input impedance of the indicator  XC       36 MW                  2 MW                   2 MW
           Electrical response conditions of the      2.5 µA                 2.5 µA                 2.5 µA
           interface                       I
           Electrical response conditions of the   U   90 V                   5 V                    5 V
           interface
           Socket arrangement and                  A                                             A
           minimum spare area A
           for indicator or plug                     Ø4.1                     6.5                 Ø4.1
                                                                          A
                                                                66                                           66
                                                       19                                            14
                                                                              20

                                                       45                                            45
           Plug arrangement

                                                                                 Ø6.3
                                                   19       Ø4.1                                 19      Ø4.1
                                                        19                                           14








           DEHNcap/A Voltage Indicator

           Nominal voltages up to 45 kV / 50 Hz
           Safe verification of isolation from supply voltage
           •  User-friendly
           •  Easy application



           Self-testing element
           DEHNcap/A electronic voltage indicators have an integrated self-testing
           element. By simply pressing the test button, the electronic circuit is tested
           for correct operation. The self-test is automatically performed as soon as
           the indicator is switched on. The voltage indicator is only operational if
           the test button is pressed, i.e. the function test was performed successful-
           ly.
                                                                Self-test of a DEHNcap/A voltage indicator            3. DEHNcap Voltage Detecting System
           General Information:
           Standard                 EN/IEC 61243-5 (DIN VDE 0682-415)
           Temperature range        – 25 °C ... + 55 °C
           Field of application     Active voltage indicator for testing
           Self-testing element     Yes


                                                                                                            767 112   SAG DCA A LRM
           Type                        SAG DCA A LRM                                                        767 112        4013364074361  05 00 03 12      150 g
                                                                                                             409,00 €
           Part No.                    767 112
           Dimensions                  120 x 60 x 25 mm
           Plug spacing                14 mm
           Type of plug                2 multilam plugs (Ø4 mm)
           Indication threshold (LRM system)  5 V
           Input impedance (LRM system)  2 MOhms











           Valid as of January 1, 2019                       You will find detailed product information on our website   49
   46   47   48   49   50   51   52   53   54   55   56