                                          3-PHASE VOLTAGE MONITORING RELAY HRN-43N
                                          - over/undervoltage
                                          - phase failure
                                          - phase sequence
                                          - phase asymmetry



       Features:
      »»
     » »  Supply voltage: AC230V
     » »  HRN-43N - for circuits 3x400/230V (incl. neutral)
      »»
     » »  Immune against the voltage from rotary machines connected to two phases
      »»
     » »  Fixed (t1), adjustable (t2) - delay
      »»
      »»
     » »  Function 'MEMORY' - manual reset. 'RESET' button on front panel
      »»
     » »  2 output relays, selectable function of 2nd relay (independent/parallel)
     » »  Output contact: 2x changeover 16A
      »»
      »»
     » »  3-MODULE, DIN rail mounting
        Technical parameters         HRN-43N
        Supply
        Supply Terminals:             A1 - A2
        Supply voltage:     AC 230V or AC 400V or AC/DC 24V
        Consumption:                 max. 4.5VA
        Supply voltage tolerance:   -15%; +10%
        Measuring   circuit                               Description
        Set of voltage:             3 x 400/230V
        Terminals:                  L1, L2, L3, N
        Upper level Umax:            138 - 276V
        Lower level Umin:          30 - 99% Umax
        Max. permanent:             AC 3 x 480V
        Hysteresis:           adjust. 5% or 10% of set value
        Asymmetry:                    5 - 20%
        Peak overload <1ms:         350 V < 1ms
        Time delay t1:            fixed, max. 200ms
        Time delay t2:            adjustable, 0-10sec
        Accuracy
        Set. accuracy (mechanical):     5%
        Repeat accuracy:               <1%
        Temperature dependance:      <0.1% /  C
                                           0
        Limit values tolerance:         5%
        Output
        Number of contacts:      2 x changeover, (AgNi)
        Rated current:               16 A / AC1
        Switching capacity:    4000 VA / AC1, 384 W/DC    Connection
        Inrush current:              30A / <3s
        Switching voltage:        250V AC1/24V DC
        Min. breaking capacity DC:    500 mW
        Mechanical life:              3 X 10 7
        Electrical life (AC1):       0.7 x 10 5
        Other   information
        Operating temperature:       -20..+55 C
                                           0
        Storage temperature:         -30..+70 C
                                           0
        Electrical strength:      4kV (input -  output)
        Operating positing:            any
        Mounting:                 DIN rail EN 60715
        Protection:                    IP40
        Overvoltage category:           III
        Pollution degree:               2
        Max. cable size:    max. 2.5mm / with sleeve 1.5mm 2
                                     2
        Dimensions:                90 x 52 x 65mm
        Weight:                        239g
        Standards:             EN 60255-6, EN 61010-1
                            IPD INDUSTRIAL PRODUCTS            Phone: 1300 556 601            www.ipdgroup.com.au