          3-PHASE VOLTAGE MONITORING RELAY HRN-54/54N

         - over/undervoltage
         - phase failure
         - phase sequence
                                                                Features:
                                                               » »  Supply from monitored voltage
                                                               »»
                                                               »»
                                                               » »  Monitors voltage in 3-phases
                                                               »»
                                                               » »  Upper and lower voltage levels adjustable
                                                               » »  Adjustable time delay
                                                               »»
                                                               » »  Red LED indication of fault
                                                               »»
                                                               » »  For circuits: 3x 400V & 3x 400V/230V (neutral monitoring: HRN-54N)
                                                               »»
                                                               » »  Output contact: 1x changeover 8A
                                                               »»
                                                               » »  Clamp terminal
                                                               »»
                                                               »»
                                                               » »  1-MODULE, DIN rail mounting
         Function                                                 Technical parameters       HRN-54 / 54N
                                                                  Supply   and   measuring
                                                                  Supply Terminals:       L1, L2, L3 / L1, L2, L3, N
                                                                  Supply/measured voltage:   3 x 230V / 400V
                                                                  Consumption:                 max. 2VA
                                                                  Upper level Umax:     420 - 500V (105-125% Un) /
                                                                                            242 - 288V + 5%
                                                                  Lower level Umin:      300 - 380V (75 - 95% Un) /
                                                                                            173 - 219V + 5%
                                                                  Time delay:               adjustable 0.5-10s
                                                                  Setting accuracy:               5%
                                                                  Output
                                                                  Number of contacts:      1 x changeover, (AgNi)
                                                                  Rated current:               8A / AC1
                                                                  Switching capacity:    2500 VA/AC1, 240 W/DC
                                                                  Inrush current:         30A / <3s / AC 3 x 288V
                                                                  Switching voltage:       250V AC1 / 24V DC
         Connection, Description                                  Min. breaking capacity DC:    500 mW
                                                                  Indication of state:          red LED
                                                                  Mechanical life:              1 x 10 7
                                                                  Electrical life (AC1):        1 x 10 5
                                                                  Other   information
                                                                  Operating temperature:      -20.. + 55 C
                                                                                                      0
                                                                                                      0
                                                                  Storage temperature:        -30.. + 70 C
                                                                  Electrical strength:     4 kV (supply - output)
                                                                  Operating position:            any
                                                                  Mounting:                 DIN rail EN 60715
                                                                  Protection degree:             IP40
                                                                  Overvoltage category:           III
                                                                  Pollution degree:               2
                                                                                                2
                                                                  Max. cable size:     max. 2.5mm /with sleeve 1.5mm 2
                                                                  Dimensions:               90 x 17.6 x 64mm
                                                                  Weight:                        69g
                                                                  Standards:             EN 60255-6, EN 61010-1
         Function description
         The relay monitors voltages between-phases in 3-phase mains. It is possible to adjust two independent voltage levels and control e.g. overvoltage or
         undervoltage separately. In the normal state, when the voltage moves between adjusted levels, the output relay is closed and the red LED is off. If the
         voltage limits are exceeded, the output relay is opened and the red LED is on. By phase switching the red LED is on (relay contact is opened). If the
         supply voltage drops under 70% of Un ( UOFF - lower level) the relay immediately opens with no delay, and a faulty state is signalled by the red LED.
         If the timing is running in this faulty state, it is immediately stopped.