Page 10 - Assembly Instructions Manual
P. 10

The UBH holders can be installed in all 3 direc-
                                                                      tions at 25 mm intervals.
                                                                      The maximum distance between two holders is
                                                                      400 mm.
                                                                      These holders are designed to allow for a
                                                                      slight movement of busbars. All the M6 bolts
                                                                      used must be tightened with 10 Nm






































































                                                                                            Bolt quality 8.8

                07      ISSUED BY: F. P DATE: 01.10.2007 APPROVED BY: A. K  DATE: 01.10.2007 REPLACES: 01.04.2005
   5   6   7   8   9   10   11   12   13   14   15