Page 8 - Assembly Instructions Manual
P. 8
These busbar holders are mainly used for small distribution
boards and power supply distribution for small fully withdraw-
able units.
Connect the cables directly on to the busbars with the tribu-
lar screws shown in the catalogue.
Do not use any other type of screws or cut threads.
The maximum distance between holders should be 300mm
The holders can be bolted directly on
to the crossbars, between crossbars
or directly on to cable holders.
With PC covers from the top to the
bottom of the enclosure you can
achieve Form 2 segregation.
Clip away for cable connection.
Torque 9Nm
Bolt quality 8.8
06 ISSUED BY: F. P DATE: 01.10.2007 APPROVED BY: A. K DATE: 01.10.2007 REPLACES: 01.04.2005