Page 8 - Assembly Instructions Manual
P. 8

These busbar holders are mainly used for small distribution
                                                   boards and power supply distribution for small fully withdraw-
                                                   able units.

                                                   Connect the cables directly on to the busbars with the tribu-
                                                   lar screws shown in the catalogue.

                                                   Do not use any other type of screws or cut threads.

                                                   The maximum distance between holders should be 300mm






















                     The holders can be bolted directly on
                     to the crossbars, between crossbars
                     or directly on to cable holders.


                     With PC covers from the top to the
                     bottom of the enclosure you can
                     achieve Form 2 segregation.




                   Clip away for cable connection.

                                                     Torque 9Nm
                                                     Bolt quality 8.8




























                06      ISSUED BY: F. P DATE: 01.10.2007 APPROVED BY: A. K  DATE: 01.10.2007 REPLACES: 01.04.2005