Page 16 - Assembly Instructions Manual
P. 16

When assembling Busbar systems
                always use bolt and nut of minimum
                8.8 quality and a torque of 49Nm.
                Clean the surfaces before joining
                and do not use any type of grease
                or contact agent.









































                                                             The connection between the main busbars and the drop-
                                                             pers are made with “Horizontal To Vertical Connectors”.

                                                             They are available in different sizes according to the num-
                                                             ber of main busbars used (2-3-4) and the current rating.
                                                             Please refer to the table below.







                                                                           Horizontal to vertical connector
                                                                                       NO OF MAIN      AMPS
                                                                    ORDER NO      X
                                                                                          BARS      DROPPERS
                                                                      20910       30        2         0-1200
                                                                      20900       50        2         0-2000
                                                                      20920       50        3         0-2000
                                                                      20930       50        4         0-2000

                10      ISSUED BY: F. P DATE: 01.10.2007 APPROVED BY: A. K  DATE: 01.10.2007 REPLACES: 01.04.2005