Page 4 - Demountable Assembly Instruction
P. 4

CHASSIS RETAINING BOLTS

               1. Fix the 2 Chassis Position Fixing Pillars in line with the retaining holes on the chassis. The pillars are part of
                   the chassis accessory pack.
               2. After fully inserting the chassis, it should be secured into position using M6 x 8 socket head screws.






         NOTE:

               1. This switchboard layout should allow for blank modules (200mm) at the top and bottom.
               2. As an option it is possible to get an additional 200mm high cell in a tier by reducing the blank space to
                   100mm. 100mm high covers are available. Please ensure that you have allowed sufficient space for busbars etc.
               3. The dropper busbar system is always with 400mm width. For 600W cells, please use a 200W x Full Height
                    separation plate to cover the blank space.
               4. Allow for connection between the plug and the incoming device.
               5. Width crossbars in the front are not needed as the return of the support shelf provides the contact surface
                   for the door.






         PRICING INFORMATION

                1. Please refer to the Elsteel Price List for list prices.
                2. Select 1 off Mounting Channel (+ Kentan Busbar Support UBS3A/B) for every 200mm space.
                3. Select 1 off support shelf (400W or 600W) for every cell + 1 end shelf.
                4. Select 1 off earthing blade kit for every cell.
                5. Select 1 off Hinge Packer Kit (option if the door is to be hinged to the chassis).
                6. Select 1 off poly barrier per cell to match cell height.
                7. Select 1 off chassis.
                8. Select 1 off mounting pan to match chassis.
                9. Select 1 off Kentan Plug for each cell (UP3250I, UP3400I, UP3800). Note that the 200H chassis accepts the
                    UP3250I & UP3400I plug only while chassis’ above this size are provided with a knockout to accept UP3800).
                10. Select door per cell to suit.




























                                                                                                           Ref: 020217
   1   2   3   4   5   6