Page 126 - B_ELSB_Cat_2022_01_MCBs
P. 126

1/126            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS   9AKK 107991 A8329
  1



          —
          MCBs technical details
          Coordination tables: selectivity




          S800N - S200 @ 230/400 V
                         E.   S800N
               Char.          B
          L.        Icu       36
                    [kA]  In [A]  25     32        40        50        63        80         100       125
                         6                         0.4       0.5       0.7       1          1.5       2.6
                         10                                  0.4       0.6       0.7        1         1.4
                         13                                            0.5       0.7        0.9       1.3
                         16                                                      0.7        0.9       1.3
                         20                                                                 0.9       1.3
          S200  B   10
                         25                                                                 0.9       1.3
                         32                                                                 0.8       1.1
                         40                                                                 0.8       1.1
                         50                                                                           1
                         63                                                                           0.9

                         E.   S800N
               Char.          B
          L.        Icu       36
                    [kA]
                         In [A]  25      32        40        50        63        80         100       125
                         0.5  T          T         T         T         T         T          T         T
                         1    3.3        T         T         T         T         T          T         T
                         1.6  0.6        1.3       T         T         T         T          T         T
                         2    0.4        0.7       1.2       T         T         T          T         T
                         3               0.4       0.6       0.7       1.1       2.6        T         T
                         4               0.4       0.6       0.7       1         1.7        3.1       T
                         6                         0.4       0.5       0.7       1          1.5       2.6
                         8                                   0.4       0.6       0.7        1         1.4
          S200  C   10   10                                  0.4       0.6       0.7        1         1.4
                         13                                            0.5       0.7        0.9       1.3
                         16                                                      0.7        0.9       1.3
                         20                                                                 0.9       1.3
                         25                                                                 0.9       1.3
                         32                                                                 0.8       1.1
                         40                                                                 0.8       1.1
                         50                                                                           1
                         63                                                                           0.9




















          E. = feed side
          L. = load side
          T  = Total selectivity up to breaking capacity of the switch on load side
              Selectivity limit values indicated in kA
   121   122   123   124   125   126   127   128   129   130   131