Page 128 - B_ELSB_Cat_2022_01_MCBs
P. 128
1/128 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: selectivity
E. S800N
Char. C
L. Icu 36
[kA] In [A] 25 32 40 50 63 80 100 125
6 0.4 0.5 0.7 0.9 1.4 2.4 4.8
10 0.3 0.4 0.5 0.7 0.9 1.3 2
13 0.3 0.4 0.5 0.7 0.9 1.3 1.9
16 0.3 0.4 0.5 0.7 0.9 1.3 1.9
20 0.4 0.5 0.7 0.9 1.2 1.8
S200 B 10
25 0.4 0.5 0.7 0.9 1.2 1.8
32 0.5 0.6 0.8 1 1.4
40 0.6 0.8 1 1.4
50 0.7 0.9 1.3
63 0.9 1.2
E. S800N
Char. C
L. Icu 36
[kA] In [A] 25 32 40 50 63 80 100 125
0.5 T T T T T T T T
1 T T T T T T T T
1.6 0.6 T T T T T T T
2 0.5 1 T T T T T T
3 0.3 0.5 0.7 1.2 2.1 T T T
4 0.3 0.4 0.7 1 1.5 2.6 T T
6 0.4 0.5 0.7 0.9 1.4 2.4 4.8
8 0.3 0.4 0.5 0.7 0.9 1.3 2
S200 C 10 10 0.3 0.4 0.5 0.7 0.9 1.3 2
13 0.3 0.4 0.5 0.7 0.9 1.3 1.9
16 0.3 0.4 0.5 0.7 0.9 1.3 1.9
20 0.4 0.5 0.7 0.9 1.2 1.8
25 0.4 0.5 0.7 0.9 1.2 1.8
32 0.5 0.6 0.8 1 1.4
40 0.6 0.8 1 1.4
50 0.7 0.9 1.3
63 0.9 1.2
E. = feed side
L. = load side
T = Total selectivity up to breaking capacity of the switch on load side
Selectivity limit values indicated in kA