Page 127 - B_ELSB_Cat_2022_01_MCBs
P. 127

1
                                                                                                            1/127



          —
          MCBs technical details
          Coordination tables: selectivity




                         E.   S800N
               Char.          B
          L.        Icu       36
                    [kA]  In [A]  25     32        40        50        63        80         100       125
                         0.5  T          T         T         T         T         T          T         T
                         1    0.8        5         T         T         T         T          T         T
                         1.6  0.5        1         2.3       T         T         T          T         T
                         2    0.3        0.5       0.7       2.3       T         T          T         T
                         3               0.4       0.5       0.7       1.2       2.5        T         T
                         4               0.4       0.4       0.7       1         1.7        3         T
                         6                                   0.6       0.8       1.2        2         3.6
                         8                                             0.7       0.9        1.3       2
          S200  D   10   10                                                      0.9        1.3       2
                         13                                                                 1         1.5
                         16                                                                           1.5
                         20
                         25
                         32
                         40
                         50
                         63

                         E.   S800N
               Char.          B
          L.        Icu       36
                    [kA]  In [A]  25    32         40        50        63        80        100        125
                         0.5  T         T          T         T         T         T         T          T
                         1    0.8       5          T         T         T         T         T          T
                         1.6  0.5       1          2.3       T         T         T         T          T
                         2    0.3       0.5        0.7       2.3       T         T         T          T
                         3              0.4        0.5       0.7       1.2       2.5       T          T
                         4              0.4        0.4       0.7       1         1.7       3          T
                         6                                   0.6       0.8       1.2       2          3.6
                         8                                             0.7       0.9       1.3        2
          S200  K   10   10                                                      0.9       1.3        2
                         13                                                                1          1.5
                         16                                                                           1.5
                         20
                         25
                         32
                         40
                         50
                         63










          E. = feed side
          L. = load side
          T  = Total selectivity up to breaking capacity of the switch on load side
              Selectivity limit values indicated in kA
   122   123   124   125   126   127   128   129   130   131   132