Page 142 - B_ELSB_Cat_2022_01_MCBs
P. 142

1/142            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS   9AKK 107991 A8329
  1



          —
          MCBs technical details
          Coordination tables: selectivity




                          E.   S800N
                Char.          D
          L.         Icu       36
                     [kA]  In [A]  25   32         40        50        63         80        100       125
                          0.2  T        T          T         T         T          T         T         T
                          0.3  T        T          T         T         T          T         T         T
                          0.5  T        T          T         T         T          T         T         T
                          0.75  T       T          T         T         T          T         T         T
                          1    T        T          T         T         T          T         T         T
                          1.6  T        T          T         T         T          T         T         T
                          2    2.3      T          T         T         T          T         T         T
                          3    0.7      1.3        4.4       T         T          T         T         T
                     25
                          4    0.7      1          2.2       4.4       7.7        T         T         T
                          6    0.6      0.8        1.5       2.5       3.6        12        24.2      T
          S200P  K
                          8    0.5      0.7        1.1       1.5       2          4         5.5       9.9
                          10   0.5      0.7        1.1       1.5       2          4         5.5       9.9
                          13            0.6        0.9       1.2       1.5        2.6       3.4       5.2
                          16                       0.9       1.2       1.5        2.6       3.4       5.2
                          20                                 0.9       1.1        1.8       2.2       3.2
                          25                                           1.1        1.8       2.2       3.2
                          32                                                      1.7       2         2.9
                          40                                                                1.9       2.6
                     15
                          50                                                                          2.2
                          63








































         E. = feed side
         L. = load side
         T  = Total selectivity up to breaking capacity of the switch on load side
             Selectivity limit values indicated in kA
   137   138   139   140   141   142   143   144   145   146   147