Page 138 - B_ELSB_Cat_2022_01_MCBs
P. 138

1/138            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS   9AKK 107991 A8329
  1



          —
          MCBs technical details
          Coordination tables: selectivity




          S800N - S200P @ 230/400 V
                          E.    S800N
                Char.           B
          L.         Icu        36
                     [kA]  In [A]  25     32        40        50        63        80        100       125
                          0.5   T         T         T         T         T         T         T         T
                          1     3.3       T         T         T         T         T         T         T
                          1.6   0.6       1.3       T         T         T         T         T         T
                           2    0.4       0.7       1.3       T         T         T         T         T
                           3              0.4       0.6       0.7       1.1       2.6       8.8       T
                           4              0.4       0.6       0.7       1         1.7       3.1       7
                     25    6                        0.4       0.5       0.7       1         1.5       2.6
                           8                                  0.4       0.6       0.7       1         1.4
          S200P C          10                                 0.4       0.6       0.7       1         1.4
                           13                                           0.5       0.7       0.9       1.3
                           16                                                     0.7       0.9       1.3
                           20                                                               0.9       1.3
                           25                                                               0.9       1.3
                           32                                                               0.8       1.1
                           40                                                               0.8       1.1
                     15
                           50                                                                         1
                           63                                                                         0.9











































          E. = feed side
          L. = load side
          T  = Total selectivity up to breaking capacity of the switch on load side
              Selectivity limit values indicated in kA
   133   134   135   136   137   138   139   140   141   142   143