          Coordination tables: selectivity




                          E.    S800N
                Char.           B
          L.         Icu        36
                     [kA]  In [A]  25     32        40        50        63        80        100       125
                          0.2   T         T         T         T         T         T         T         T
                          0.3   T         T         T         T         T         T         T         T
                          0.5   T         T         T         T         T         T         T         T
                          0.75  T         T         T         T         T         T         T         T
                          1     0.8       5         T         T         T         T         T         T
                          1.6   0.5       1         2.3       T         T         T         T         T
                          2     0.3       0.5       0.7       2.1       T         T         T         T
                          3               0.4       0.5       0.7       1.2       2.5       8.6       T
                     25
                          4               0.4       0.4       0.7       1         1.7       3         7.7
                          6                                   0.6       0.8       1.2       2         3.6
          S200P K
                          8                                             0.7       0.9       1.3       2
                          10                                                      0.9       1.3       2
                          13                                                                1         1.5
                          16                                                                          1.5
                          20
                          25
                          32
                          40
                     15
                          50
                          63


                          E.    S800N
                Char.           C
          L.         Icu        36
                     [kA]
                          In [A]  25      32        40        50        63        80        100       125
                          6                         0.4       0.5       0.7       1         1.5       2.6
                          10                                  0.4       0.6       0.7       1         1.4
                          13                                            0.5       0.7       0.9       1.3
                     25
                          16                                                      0.7       0.9       1.3
                          20                                                                0.9       1.3
          S200P B
                          25                                                                0.9       1.3
                          32                                                                0.8       1.1
                          40                                                                0.8       1.1
                     15
                          50                                                                          1
                          63                                                                          0.9
















          E. = feed side
          L. = load side
          T  = Total selectivity up to breaking capacity of the switch on load side
              Selectivity limit values indicated in kA