Page 150 - B_ELSB_Cat_2022_01_MCBs
P. 150
1/150 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: selectivity
Fuse - S300P @ 415V AC
Supply s. NH 00
Char. gG
Load s. Icu [kA] lu [A] 100
In [A] 25 35 40 50 63 80 100 125 160
3 0.9 4 T25 T25 T25 T25 T25 T25 T25
4 0.7 2.5 3.5 T25 T25 T25 T25 T25 T25
6 0.6 1.3 1.5 2.5 5.5 12 T25 T25 T25
8...13 0.4 0.8 1 1.5 2.3 3.5 5 10 T25
S300P B, C 25
16 0.7 0.9 1.4 2 3 4 8 T25
20...25 0.7 1.2 1.9 2.7 3.8 7 15
32...40 1.7 2.5 3.5 6 10
50...63 4 6 8
Fuse - S300P @ 415V AC
Supply s. NH 00
Char. gG
Load s. Icu [kA] lu [A] 100
In [A] 25 35 40 50 63 80 100 125 160
3 0.9 4 5 T25 T25 T25 T25 T25 T25
4 0.7 2.5 3.5 6 T25 T25 T25 T25 T25
6 0.6 1.3 1.5 2.5 5.0 9 T25 T25 T25
8..13 0.4 0.8 1 1.5 2 3.2 4.5 9 T25
S300P D, K 25
16 0.7 0.9 1.2 1.8 2.8 3.8 7.5 20
20..25 0.7 1.1 1.7 2.5 3.5 6 12
32..40 1.5 2.2 3 5 8
50..63 2.2 3.3 5.5
Fuse - S300P @ 415V AC
Supply s. NH 00
Char. gG
Load s. Icu [kA] lu [A] 100
In [A] 25 35 40 50 63 80 100 125 160
3 0.9 4 T25 T25 T25 T25 T25 T25 T25
4 0.8 2.5 4 7 T25 T25 T25 T25 T25
6 0.6 1.3 2 2.8 6 T25 T25 T25 T25
8..10 0.4 0.8 1.2 1.5 2.3 3.5 6 20 T25
S300P Z 25
16 0.7 0.9 1.5 1.9 2.9 4.5 10 T25
20..25 0.7 1.3 2 2.8 4.4 8 15
32..40 1.8 2.7 4 6 12
50..63 3 4.5 8