Page 151 - B_ELSB_Cat_2022_01_MCBs
P. 151
1
1/151
—
MCBs technical details
Coordination tables: selectivity
Fuse - S300P @ 415V AC
Supply s. DIAZET
Char.
Load s. Icu [kA] lu [A] 50
In [A] 10 16 20 25 35 50 63 80 100
3 0.5 0.5 0.8 0.9 2.2 4.5 T25 T25 T25
4 0.5 0.5 0.6 0.8 1.8 3.6 9.7 T25 T25
6 0.5 0.5 0.6 1.4 2.4 5.5 T25 T25
8...13 1.3 1.9 3.3 5 9.4
S300P B, C 25
16 1.2 1.8 3.2 4.4 8
20...25 1.7 2.8 3.8 6.5
32...40 3.5 5.9
50...63 5.5
Fuse - S300P @ 415V AC
Supply s. DIAZET
Char.
Load s. Icu [kA] lu [A] 50
In [A] 10 16 20 25 35 50 63 80 100
3 0.5 0.5 0.6 0.9 2.3 4.3 T25 T25 T25
4 0.5 0.6 0.9 2 3.8 9.5 T25 T25
6 0.5 0.7 1.5 2.6 5.3 9.1 T25
8..13 1.2 1.8 3.2 4.6 8.6
S300P D, K 25
16 1.6 2.7 4 7.4
20..25 2.4 3.4 6.2
32..40 4.8
50..63
Fuse - S300P @ 415V AC
Supply s. DIAZET
Char.
Load s. Icu [kA] lu [A] 50
In [A] 10 16 20 25 35 50 63 80 100
3 0.5 0.5 0.8 0.9 2.2 4.5 T25 T25 T25
4 0.5 0.5 0.6 0.8 1.8 3.6 9.7 T25 T25
6 0.5 0.5 0.6 1.4 2.4 5.5 T25 T25
8..10 1.3 1.9 3.3 5 9.4
S300P Z 25
16 1.2 1.8 3.2 4.4 8
20..25 1.7 2.8 3.8 6.5
32..40 3.5 5.9
50..63 5.5