Page 152 - B_ELSB_Cat_2022_01_MCBs
P. 152
1/152 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Coordination tables: selectivity
Fuse - S300P @ 415V AC
Supply s. NEOZET
Char.
Load s. Icu [kA] lu [A] 50
In [A] 10 16 20 25 35 50 63 80 100
3 0.5 0.5 0.5 0.6 1.9 5.2 T25 T25 T25
4 0.5 0.5 0.5 0.6 1.6 4 7.6 T25 T25
6 0.5 0.5 0.5 1.2 2.7 4.5 T25 T25
8...13 1.1 2.2 3 4.9 T25
S300P B, C 25
16 1.1 2.1 2.8 4.4 9.5
20...25 1.9 2.5 3.8 7.8
32...40 3.5 7
50...63 6.5
Fuse - S300P @ 415V AC
Supply s. NEOZET
Char.
Load s. Icu [kA] lu [A] 50
In [A] 10 16 20 25 35 50 63 80 100
3 0.5 0.5 0.5 0.7 1.8 4.8 9.3 T25 T25
4 0.5 0.5 0.7 1.7 4.6 7.7 T25 T25
6 0.5 0.5 1.3 2.9 4.5 9 T25
8..13 1.1 2.1 2.9 4.6 T25
S300P D, K 25
16 1.9 2.6 3.9 9
20..25 2.2 3.4 7.5
32..40 5.7
50..63
Fuse - S300P @ 415V AC
Supply s. NEOZET
Char.
Load s. Icu [kA] lu [A] 50
In [A] 10 16 20 25 35 50 63 80 100
3 0.5 0.5 0.5 0.6 1.9 5.2 T25 T25 T25
4 0.5 0.5 0.5 0.6 1.6 4 7.6 T25 T25
6 0.5 0.5 0.5 1.2 2.7 4.5 T25 T25
8..10 1.1 2.2 3 4.9 T25
S300P Z 25
16 1.1 2.1 2.8 4.4 9.5
20..25 1.9 2.5 3.8 7.8
32..40 3.5 7
50..63 6.5