1/16 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS - TECHNICAL DETAILS 9AKK 107991 A8329
1
—
MCBs technical details
Tripping characteristics
Example:
Correction factor (k) = I non-tripping
Impulse length
Example: Non-tripping current (Electromagnetic release)
S 201-B16
I non-tripping = k x non-tripping current B-Characteristic = 3 x I n
I non-tripping = 4,2 x 3 x 16 C-Characteristic = 5 x I n
I non-tripping = 201,6 A D-Characteristic = 10 x I n
K-Characteristic = 10 x I
n
Z-Characteristic = 2 x I
n
The S 201-B16 does not trip at an impulse of 600 es at a current up to 201,6 A.