          MCBs technical details
          Tripping characteristics






                                            Example:





           Correction factor (k) = I  non-tripping


























                              Impulse length


          Example:                    Non-tripping current (Electromagnetic release)

          S 201-B16
          I  non-tripping  = k x non-tripping current  B-Characteristic =   3 x I n
          I  non-tripping  = 4,2 x 3 x 16    C-Characteristic =   5 x I n
          I  non-tripping  = 201,6 A    D-Characteristic = 10 x I n
                                      K-Characteristic = 10 x I
                                                          n
                                      Z-Characteristic =   2 x I
                                                          n
          The S 201-B16 does not trip at an impulse of 600 es at a current up to 201,6 A.