AC UPS AMPLON FAMILY - RT SERIES
RT SERIES ON-LINE SINGLE PHASE UPS
Features: Output Voltage Power Rating
- True online double-conversion topology AC (V) (kVA) (kW) Output Connections Model Part No.
- Zero transfer time 1 0.9 IEC C13 x 6 RT-1K UPS102R2RT2B0BB
- Watch-dog design of DSP (Digital Signal 200 /208 /220/
(1)
(1)
Processor) 230/240 2 1.8 IEC C13 x 6, IEC C19 x 1 RT-2K UPS202R2RT2B0BB
- Cold-start capability 3 2.7 IEC C13 x 6, IEC C19 x 1 RT-3K UPS302R2RT2B0BB
- Hot swappable batteries (1) When the UPS is de-rated to 90% of its capacity
- LCD display and LED indicators
- Includes Rail kit
- Supports both rack and tower installation
UPS102R2RT2B0BB
RT SERIES ON-LINE SINGLE PHASE UPS SELECTION CHART
Model RT-1K RT-2K RT-3K
Input
Voltage Range AC (V) 175 - 280 (Full load), 120 - 175 (70 - 100% Load)
Frequency Range (Hz) 40 - 70
Output
(1)
(1)
Output Voltage AC (V) 200 /208 /220/230/240
Voltage Regulation ± 1% (Linear load)
Frequency Range (Hz) 50/60 ± 0.05
Waveform Pure Sine Wave
Voltage Harmonic Distortion < 2% (Linear load)
Battery Internal (2)
Voltage DC (V) 24 48 72
Type 12V/ 9 Ah Sealed Lead-acid
Charge Current (A) 1.5 2
Charging Time (hours) < 3 hours to 90% (Standard)
(3)
Discharge Time (minutes) 6 6 6
Communication
Interfaces SMART Slot x 1, RS-232 Port x 1, USB Port x 1, REPO x 1
Physical
Dimensions (mm) 440W x 89H x 335D 440W x 89H x 432D 440W x 89H x 610D
Net Weight (kg) 12 18 28
Environment
Operating Temperature (⁰C) 0 - 55 (4)
Noise Level (dBA) <40 <43 <46
(1) When the UPS is de-rated to 90% of its capacity
(2) Each model has internal batteries and can connect to the Delta external battery pack (optional)
(3) UPS at 75% loaded and no external batteries
(4) 40 to 50°C with 80% de-rating