Power Supplies & Transformers



        AC UPS AMPLON FAMILY - RT SERIES


                                                 RT SERIES ON-LINE SINGLE PHASE UPS
        Features:                                 Output Voltage   Power Rating
           - True online double-conversion topology  AC (V)                Output Connections   Model Part No.       1
           - Zero transfer time                                 (kVA)  (kW)                                         1
           - Unity output power factor            Standard Runtime Model
           - Automatic fan speed control                        5     5    C13 x 6, C19 x 2,    RT-5K  UPS502R2RT0B035
           - Programmable load bank prioritises critical                   Terminal x 1,
         loads during blackouts                   200/208/220/   6    6    C19 x 1 (Load Bank)  RT-6K  UPS602R2RT0B035
           - Hot swappable batteries              230/240       8     8    C13 x 6, C19 x 4,    RT-8K  UPS802R2RT0B035
           - LCD display and LED indicators                                Terminal x 1,
           - Required Rail kit 915100011                        10    10   C19 x 1 (Load Bank)  RT-10K UPS103R2RT0B035
           - Supports both rack and tower installation
                                                  Extended Runtime Model
                                                                5     5                       RT-5K  UPS502R2RT2N035
                                                  200/208/220/   6    6    Terminal x 1,      RT-6K  UPS602R2RT2N035
                                                  230/240       8     8    Terminal x 1 (Load Bank)  RT-8K  UPS802R2RT2N035
                                                                10    10                      RT-10K UPS103R2RT2N035





                      UPS502R2RT0B035





        RT SERIES ON-LINE SINGLE PHASE UPS SELECTION CHART
         Model                                RT-5K             RT-6K              RT-8K             RT-10K
         Input
         Voltage Range AC (V)                     100 - 280 (Single phase, 2-wire + G), 100 - 175 (With linear de-rating 50 - 100%)
         Frequency Range (Hz)                                            40 - 70
         Output
         Output Voltage AC (V)                                      200/208/220/230/240
         Voltage Regulation                                           ± 1% (Linear load)
         Frequency Range (Hz)                                          50/60 ± 0.05
         Waveform                                                     Pure Sine Wave
         Voltage Harmonic Distortion                                  < 2% (Linear load)
         Battery                                  Internal (Standard Runtime Model) /External (Extended Runtime Model)
                                                                          (1)
         Voltage DC (V)                                 192                                  240
         Type                                   12V/7 Ah Sealed Lead-Acid            12V/ 9 Ah Sealed Lead-Acid
                                             1 Default (Standard Runtime Model)   1.5 Default (Standard Runtime Model)
         Charge Current (A)
                                             Up to 8 (Extended Runtime Model)      Up to 8 (Extended Runtime Model)
         Charging Time (hours)                                    < 3 hours to 90% (Standard)
         Communication
         Interfaces                    MINI Slot x 1, USB Port x 1, RS232 Port x 1, RS485 Port x 1, REPO/ROO Port x 1, Dry Contact x 4, Parallel Port  x 2
                                                                                                             (2)
         Physical
                                         440W x 176H x 665D (Standard Runtime Model)  440Wx 218H x 750D (Standard Runtime Model)
         Dimensions (mm)
                                         440W x 88.2H x 430D (Extended Runtime Model)  440Wx 88.2H x 565D (Extended Runtime Model)
                                               54 (Standard Runtime Model)          85.5 (Standard Runtime Model)
         Net Weight (kg)
                                               10.9 (Extended Runtime Model)        15.2 (Extended Runtime Model)
         Environment
         Operating Temperature (°C)                                      0 - 55 (3)
         Noise Level (dBA)                              48                                   50
        (1)  Each model has internal batteries and can connect to the Delta external battery pack (optional)
        (2)  Only applicable to RT 5-10 kVA Extended Runtime Model
        (3)  40°C to 50°C with 80% de-rating