Power Supplies & Transformers
AC UPS AMPLON FAMILY - RT SERIES
RT SERIES ON-LINE THREE PHASE UPS
Features: Output Voltage AC (V) Power Rating Output Model Part No.
- True online double-conversion topology (kVA) (kW) Connections 1 1
- Zero transfer time 10 10 RT-10K3P UPS103R6RT2N035
- Unity output power factor 380/400/415 (Three Phase) or 15 15 Terminal x 1 RT-15K3P UPS153R6RT2N035
- Three phase input with output support for three 220/230/240 (Single phase) 20 20 RT-20K3P UPS203R6RT2N035
phase or single phase
- Programmable load bank prioritises critical loads
during blackouts
- Hot swappable batteries
- LCD display and LED indicators
- Required Rail kit 915100011
- Supports both rack and tower installation
UPS103R6RT2N035
RT SERIES ON-LINE THREE PHASE UPS SELECTION CHART
Model RT-10K3P RT-15K3P RT-20K3P
Input
Voltage Range AC (V) 138 - 485 (Three phase, 4-wire + G), 138 - 305 (with linear de-rating 40-100%)
Frequency Range (Hz) 50/60 ± 10
Output
Output Voltage AC (V) 380/400/415 (Three phase), or 220/230/240 (Single phase)
Voltage Regulation ± 1% (Linear load)
Frequency Range (Hz) 50/60 ± 0.05
Waveform Pure Sine Wave
Voltage Harmonic Distortion ≤ 2% (Linear load)
Battery External
Battery Voltage DC (V) 144 , 192 - 264 ±144 , ±192 to ±264
(1)
(1)
Communication
Interfaces MINI Slot x 1, Parallel Port x 2, USB Port x 1, RS485 Port x 1, REPO/ROO Port x 1, Dry Contact x 4
Physical
Dimensions (mm) 440W x 88.2H x 649D 440W x 88.2H x 760D
Net Weight (kg) 16.6 22 22.5
Environment
Operating Temperature (⁰C) 0 - 55 (2)
Noise Level (dBA) 50 54
(1) De-rating to 70% load
(2) When the operating temperature is at 40 - 55°C, the UPS will be de-rated to 75% of its capacity
1300 556 601 | ipd.com.au | V17-R05 219