Page 250 - IPD Product Catalog V17
P. 250

Lightning & Surge Protection



        PROCESS CONTROL PROTECTION - INSTRUMENTATION


                                   SLIMLINE SIGNAL LINE PROTECTORS
        Features:                  Imax    Iimp
           - Multistage failsafe design  Common   Common   MCOV     Voltage      Maximum
           - Two different earthing options  Mode   Mode  No. of    Protection Level   Load   Earthing Part No.
           - Plug-in design        (8/20μs)  (10/350μs)  Pairs  AC (V) DC (V)  (1 kV/μs) - Up (kV)  Current
                                                                                 (mA)
           - For most twisted pair    (kA)  (kA)
          signalling schemes                              5    7    0.015        250       Direct  SL7V5-G
           - Standards IEC 61643-21,                      11   16   0.03         250       Direct  SL18-G
          AS/NZS 1768                                     24   34   0.045        250       Direct  SL36-G
                                                          24   34   0.045        250       Indirect  SL36-EC90
                                   10      2.5      1     6    8    0.035        250       Direct  SL485-G
                                                          6    8    0.035        250       Indirect  SL485-EC90
                                                          N/A  34   0.04         30        Direct  SL420-G
                                                          N/A  34   0.04         30        Indirect  SL420-EC90
                                                          2    3    0.015        250       Direct  SL-RTD-G
                                   Intrinsically Safe
                                                          24   34   0.055        250       Indirect  IS-SL36-EC90 (1)
                                   10      2        1     24   34   0.055        250       Direct  IS-SL36-G (1)
                                                          6    8    0.030        250       Direct  IS-SL485-G (1)
           SL36-G   IS-SL36-EC90
                                   (1)  IEC Ex and ATEX certified



        Features:                  Imax    Iimp
           - Load current up to 6 A  Common   Common      MCOV      Voltage      Maximum
           - Plug-in design        Mode    Mode     No. of          Protection Level   Load   Earthing Part No.
           - Two different earthing options  (8/20μs)  (10/350μs)  Pairs  (1 kV/μs) - Up (kV) Current (A)
           - For most twisted pair    (kA)  (kA)          AC (V) DC (V)
          signaling schemes                               11   14   0.035                  Direct  SSP6A-14-G
           - Standards IEC 61643-21,                      20   26   0.055                  Indirect  SSP6A-26-EC90
          AS/NZS 1768
                                   9.6                    30   38   0.075                  Indirect  SSP6A-38-EC90
                                           N/A      1                            6
                                                          50   65   0.13                   Indirect  SSP6A-65-EC90
                                                          50   65   0.13                   Direct  SSP6A-65-G
                                   3.6                    130  170  0.45                   Direct  SSP6A-130-G
                                   Intrinsically Safe
                                   9.6     N/A      1     20   26   0.055        6         Direct  IS-SSP6A-26-G (1)
                                   (1)  IEC Ex and ATEX certified




        SSP6A-38-EC90 IS-SSP6A-26-G

        Features:                  Imax    Iimp
           - Load current up to 10 A   Common   Common    MCOV      Voltage      Maximum
           - Plug-in design        Mode    Mode     No. of          Protection Level   Load   Earthing Part No.
           - Failsafe design       (8/20μs)  (10/350μs)  Pairs  AC (V) DC (V)  (1 kV/μs) - Up (kV) Current (A)
           - LED indicator         (kA)    (kA)
           - Standards IEC 61643-21,    15  N/A     1     30   38   0.11         10        Indirect  SSP10A-38
          AS/NZS 1768












                 SSP10A-38