Page 246 - Product-catalogue-v17
P. 246

Lightning & Surge Protection



        POWER PROTECTION - MV AND HV SURGE ARRESTERS


                                                     AC SYSTEMS
        Features:                                    In (8/20μs) (kA)   High Current Impulse   MCOV AC (kVrms)  Part No.
           - For AC systems                          Peak          (4/10 μs) kA Peak
           - Line discharge class (LD) 1             10            100             24             POLIM-D-24-10
           - Grey colour                             10            100             26             POLIM-D-26-11
           - Direct molded in silicone housing
           - Outdoor and indoor application
           - Standards IEC 60099-4
        Especially recommended for overvoltage protection of:
           - MV distribution transformer
           - Pole mounted MV transformer
           - MV cable and cable termination
           - Reactor and PLC line trap
           - Further MV distribution equipment






                                                             E               F                  F




                      POLIM-D-24-10


                      DIMENSIONS
                     M12x25
                    Ø116
                    Ø87

                                    H



                    M12x25

                          43
                                                  Continuous Operating  Recommended Clearances  Height
                                                  Voltage AC (kVrms)  E (mm)     F (mm)       H (mm)
                                   43             24               293           306          429
                                                  26               315           328          518

                            SW19
             Standard dimensions without accessories

        ELECTRICAL DATA

         Continuous       Residual voltage U  at specified impulse current
                                       res
         operating  Rated
         voltage  voltage  wave 1/…μs       wave 8/20 μs                               wave 30/60 μs
         U c     U r      5 kA     10 kA    1 kA    2.5 kA   5 kA     10 kA   20 kA    125 A    250 A    500 A
         kV rms  kV rms   kV peak  kV peak  kV peak  kV peak  kV peak  kV peak  kV peak  kV peak  kV peak  kV peak
         24      30       86.6     95.8     69.8    74       78.2     84      95.4     62.2     64.3     66.4
         26      32.5     93.8     103.8    75.6    80.1     84.7     91      103.3    67.4     69.7     71.9



          246                                    1300 556 601  |  ipd.com.au  |  V17-R04
   241   242   243   244   245   246   247   248   249   250   251