Page 268 - IPD Product Catalog V17
P. 268
Digiware AC Metering System
DIRIS DIGIWARE CURRENT MODULES
CURRENT MEASUREMENT MODULE WITH INTEGRATED SENSORS
Features: Description Current Inputs Part No.
- Plug and play, save wiring time Metering Application
- Current sensors are integrated in the module S-130 Module 3 48290160
- Quick RJ45 connection between modules Analysis Application
- Positioning possible upstream or downstream of S-135 Module 3 48290161
the protective device Monitor ON/OFF/TRIP status of the circuit breaker
- Multi-circuit metering and measurement
- Compact design, DIN Rail/back plate mountable
- Class 0.5 accuracy for active energy CURRENT MEASUREMENT MODULE WITH INTEGRATED SENSORS
measurement SELECTION CHART
- Branch circuit monitoring
- Complies with standards, IEC 61557-12 and DIRIS Digiware S S-130 S-135
UL 257746 Number of current inputs 3 3
Base current Ib 10A 10A
Maximum current Imax 63A 63A
1P + N 1P + N
Load type accepted 2P/2P + N 2P/2P + N
3P/3P +N 3P/3P +N
Metering
+/- kWh, +/- kvarh, kVAh • •
Multi-tariff (maximum 8) - •
Load curves - •
Multi-measurement
48290160
I1, I2, I3, In, ΣP, ΣQ, ΣS, ΣPF • •
P, Q, S, PF per phase • •
Predictive power - •
Current unbalance (Inba, Idir, Iinv, Ihom, Inb) - •
ϕ, cos ϕ, tan ϕ - •
Quality
THDi1, THDi2, THDi3, THDin - •
Individual harmonics I (up to level 63rd) - •
Crest factors U, V, I - •
K factor - •
Overcurrents - •
Alarms
Thresholds and combinations - •
Load level - -
Wiring errors - •
Protective device - •
Trends
Average values - •
FUNCTIONAL DIAGRAM
Downstream Upstream
The DIRIS Digiware S measurement module can be mounted upstream or
downstream of the protective device solving issues of space constraints.
268 1300 556 601 | ipd.com.au | V17-R05