Page 272 - IPD Product Catalog V17
P. 272

Digiware AC Metering System



        DIRIS DIGIWARE CURRENT SENSORS


                                               SPLIT CORE CURRENT SENSORS
        Features:                               Model  Nominal Current Range (A)  Actual Coverage Range (A)  Part No.
           - Smart sensor with an extended operational range  TR-10  25 - 63  0.5 - 75.6             48290555
           - Automatic detection of rating      TR-14  40 - 160               0.8 - 192              48290556
           - Safe disconnection of CT secondary under load
           - Quick connection via RJ12 and identification of   TR-21  63 - 250  1.26 - 300           48290557
          cable by colour code                  TR-32  160 - 600              3.2 - 720              48290558
           - Extended measurement range, 2% to 120% of
          nominal current range
           - Class 1 global measuring accuracy complying with
          standard 61557-12













                 TR Split Core Current Sensors
                                               SPLIT CORE CURRENT SMART SENSORS
        Features:                               Model  Nominal Current Range (A)  Actual Coverage Range (A)  Part No.
           - Smart sensor with an extended operational range  iTR-10  25 - 63  0.5 - 75.6            48290655
           - Automatic detection of rating      iTR-14  40 - 160              0.8 - 192              48290656
           - Safe disconnection of CT secondary under load
           - Quick connection via RJ12 and identification of   iTR-21  63 - 250  1.26 - 300          48290657
          cable by colour code                  iTR-32  160 - 600             3.2 - 720              48290658
           - Extended measurement range, 2% to 120% of   -  Monitor ON/OFF/TRIP status of upstream circuit breaker
          nominal current range
           - Class 0.5 global measuring accuracy complying
          with standard 61557-12
           - VirtualMonitor technology allows for status
          monitor of devices
           - AutoCorrect technology guarantees measurement
          system will function properly













                         iTR...





                                               DIMENSIONS
                                                Model            W x H x D (mm)  Aperture (mm)  A (mm)  B (mm)
                                                TR-10/iTR-10     26 x 44 x 28  Ø 10           -         -
                                                TR-14/iTR-14     29 x 67 x 28  Ø 14           14        15
                                                TR-21/iTR-21     37 x 65 x 43  Ø 21           21        23
                                                TR-32/iTR-32     53 x 86 x 47  Ø 32           32        33
            TR/ iTR-10, TR/iTR-14, TR/iTR-21, TR/iTR-32





          272                                    1300 556 601  |  ipd.com.au  |  V17-R05
   267   268   269   270   271   272   273   274   275   276   277