Page 270 - IPD Product Catalog V17
P. 270
Digiware AC Metering System
DIRIS DIGIWARE CURRENT SENSORS
SOLID CORE CURRENT SENSORS
Features: Model Nominal Current Range (A) Actual Coverage Range (A) Part No.
- Plug and play, rapid RJ12 makes wiring easy TE-18 5 - 20 0.1 - 24 48290500
and reliable
- Prevents wiring errors TE-18 25 - 63 0.5 - 75 48290501
- The sensors can be installed in both directions TE-25 40 - 160 0.8 - 192 48290502
- Extended measurement range, 2% to 120% of TE-35 63 - 250 1.26 - 300 48290503
nominal current range TE-45 160 - 630 3.2 - 756 48290504
- Class 0.5 global measuring accuracy, TE-55 400 - 1000 8 - 1200 48290505
Class 0.2 CT accuracy TE-90 600 - 2000 12 - 2400 48290506
- Compact design, DIN Rail, staggered, cable,
panel and bus bar mountable
- Complies with standard IEC 61557-12
ACCESSORY
To Suit Description Aperture (mm) Part No.
TE-18 CT/5A to 100mV Adaptor Ø 8.6 48290599
TE Solid Core Current Sensors DIMENSIONS
Model Pitch (mm) W x H x D (mm) F (mm) T (mm)
TE-18 18 28 x 45 x 20 8.6 -
TE-25 25 25 x 65 x 32.5 13.5 x 13.5 17.5
TE-35 35 35 x 71 x 32.5 21 x 21 17.5
TE-45 45 45 x 86 x 32.5 31 x 31 19.5
TE-55 55 55 x 100 x 32.5 41 x 41 21.5
TE-90 90 90 x 126 x 24.6 64 x 64 -
W D
W D W D
TE-18 TE-25, TE-35, TE-45, TE-55 TE-90
270 1300 556 601 | ipd.com.au | V17-R05