Page 308 - IPD Product Catalog V17
P. 308
Meters
DIGITAL KILOWATT HOUR METERS - CT CONNECT THREE PHASE
COUNTIS E41
Features: Description Part No.
- Allows for both total and partial kWh 1/5A CT Connect 230 - 400V AC 48503063
measurements with an accuracy of 1%
- A pulse output is incorporated into the device Number of DIN modules wide (17.5mm): 4
Configurable pulse output
- Displayed on a backlit 8-digit LCD Reading: Total/Partial kWh
- An auxiliary supply is accessible from the Dual tariff
monitoring supply Metrological LED
- Complies with standards IEC 62053-22/23 and Degree of protection: Front face - IP51
IEC 62053-31
- DIN Rail mountable
COUNTIS E43
Description Part No.
1/5A CT Connect 230 - 400V AC 48503065
Number of DIN modules wide (17.5mm): 4
RS485 JBus/Modbus communication
Configurable pulse output
Reading: Total/Partial kWh
COUNTIS E4... Four tariffs
Metrological LED
Degree of protection: Front face - IP51
COUNTIS E47
Description Part No.
1/5A CT Connect 230 - 400V AC 48503056
Number of DIN modules wide (17.5mm): 4
RJ45 Ethernet Modbus TCP communication
Configurable pulse output
Reading: Total/Partial kWh
Four tariffs
Metrological LED
Degree of protection: Front face - IP51
- The following parameters are available via RS485:
3I, In, 3V, 3U, 3P, ΣP, 3Q, ΣQ, 3S, ΣS, ΣPF
- For Current Transformers (CTs), refer to page 284 - 291.
- For CT Shorting Link Terminals, refer to page 319 & 795.
308 1300 556 601 | ipd.com.au | V17-R05