Page 309 - IPD Product Catalog V17
P. 309
Meters
PULSE METERING
COUNTIS ECi2
Features: Description Part No.
- Backlit LCD display for direct reading Pulse Collector, No Analogue Inputs 48530000
- Up to 7 multi-utility meters and 2 analogue RS485 JBus/Modbus communication
sensors (7 logical inputs + 2 analogue inputs) Internal memory
- Load curves available for each input Digital Inputs: 7
- Allows for total, partial and programmable Auxiliary supply: 110 - 400V AC
energy metering Digital Inputs voltage: 10 - 30V DC
- RS485 communication through Modbus protocol Digital Inputs current: 2 - 15mA
- Allows for remote configuration and transmission Dimensions (mm): 90 x 67 x 73 (W x H x D)
of pulse/analogue data for supervision 2
- Improved customisation with the selection of
measuring and currency units
- Complies with standard IEC 62053-31 Class B COUNTIS ECi3
Description Part No.
Pulse Collector, 2 Analogue Inputs 48530001
RS485 JBus/Modbus communication
Internal memory
Digital Inputs: 7
Auxiliary supply: 110 - 400V AC
Digital Inputs voltage: 10 - 30V DC
Digital Inputs current: 2 - 15mA
Analogue Inputs current: 25mA
Dimensions (mm): 90 x 67 x 73 (W x H x D)
COUNTIS ECi...
APPLICATION
The pulse collector enables pulses from water, gas, compressed air and electricity meters or
analogue sensors to be registered and stored. All data i.e. energy meter kilowatt hours and load
curves can be centralised via RS485, JBus/Modbus communication.
kWh pulse outputs Gas Water
7 inputs to collect pulses from different energy meters (water, air, gas, electricity...)
1 x Digital Output
2 x Analogue Inputs
(0/4 - 20mA / 0 - 10V DC)
Memory
To computer via: RS485 - JBus/Modbus
1300 556 601 | ipd.com.au | V17-R05 309