Page 40 - IPD Product Catalog V17
P. 40

Circuit Breakers & Load Centres
        Circuit Breakers & Load Centres


        ISOLATION CHASSIS


                                                    NYSOL8 RANGE
        Details:
           - Complying standards.                   Rated       No. of Poles                         Part No.
               - AS/NZS IEC 60947.3 for Isolating switches   Current (A)
               - AS/NZS 61439.2   for Switchboards  Universal Feed
           - Better kA ratings; 10kA/1s, 36kA/0.1s and fully type tested
          to suit a large range of MCB’S.                       12                                   NY8A12A25U
           - Suitable to achieve compliance with all forms of   18                                   NY8A18A25U
          separation as per AS/NZS 61439 Appendix C.            24                                   NY8A24A25U
           - Voltage Ratings.                                   36                                   NY8A36A25U
               - Rated Voltage                Un : 415V   250   48                                   NY8A48A25U
               - Insulation Voltage              Ui : 440V      60                                   NY8A60A25U
               - Rated Withstand Impulse Voltage   Uimp : 4kV   72                                   NY8A72A25U
           - AC21B at 63A to AS/NZS IEC 60947.3.                84                                   NY8A84A25U
           - AC20B at 63A.
           - Large main connection tags.                        96                                   NY8A96A25U
           - Disconnector has been tested 300 cycles under load.
           - Disconnector requires a tool, can’t be finger operated.
           - Spring loaded tee-off covers.
           - Interlocked covers and Disconnector-Unable to energise
          tee-off without fitting an MCB or RCBO.
           - Nysol8 in Electrical Orange for easy identification.
           - 18mmpitch poles.
           - Coming with insulated enclosure, insulated tee-off
          covers, insulating tongue over the line terminal and
          interlocked isolating switch operable only by tool.






























                        NY8A36A25U




















          40                                     1300 556 601  |  ipd.com.au  |  V17-R05
   35   36   37   38   39   40   41   42   43   44   45