Page 40 - IPD Product Catalog V17
P. 40
Circuit Breakers & Load Centres
Circuit Breakers & Load Centres
ISOLATION CHASSIS
NYSOL8 RANGE
Details:
- Complying standards. Rated No. of Poles Part No.
- AS/NZS IEC 60947.3 for Isolating switches Current (A)
- AS/NZS 61439.2 for Switchboards Universal Feed
- Better kA ratings; 10kA/1s, 36kA/0.1s and fully type tested
to suit a large range of MCB’S. 12 NY8A12A25U
- Suitable to achieve compliance with all forms of 18 NY8A18A25U
separation as per AS/NZS 61439 Appendix C. 24 NY8A24A25U
- Voltage Ratings. 36 NY8A36A25U
- Rated Voltage Un : 415V 250 48 NY8A48A25U
- Insulation Voltage Ui : 440V 60 NY8A60A25U
- Rated Withstand Impulse Voltage Uimp : 4kV 72 NY8A72A25U
- AC21B at 63A to AS/NZS IEC 60947.3. 84 NY8A84A25U
- AC20B at 63A.
- Large main connection tags. 96 NY8A96A25U
- Disconnector has been tested 300 cycles under load.
- Disconnector requires a tool, can’t be finger operated.
- Spring loaded tee-off covers.
- Interlocked covers and Disconnector-Unable to energise
tee-off without fitting an MCB or RCBO.
- Nysol8 in Electrical Orange for easy identification.
- 18mmpitch poles.
- Coming with insulated enclosure, insulated tee-off
covers, insulating tongue over the line terminal and
interlocked isolating switch operable only by tool.
NY8A36A25U
40 1300 556 601 | ipd.com.au | V17-R05