Page 46 - Product-catalogue-v17
P. 46

Moulded Case Circuit Breakers (MCCB)



        SACE Tmax XT MOULDED CASE CIRCUIT BREAKERS - TECHNICAL DATA










         Size                                                          XT1          XT2              XT3                        XT4                  XT5                 XT6 (2)              XT7                  XT7M
         Rated Uninterrupted Current                               [A]  160         160              250                        160 / 250            400 / 630           800 / 1000  (6)      800/ 1000 / 1250 / 1600  800 / 1000 / 1250 / 1600
         Poles                                                   [No.]  3, 4        3, 4             3, 4                       3, 4                 3, 4                3, 4                 3, 4                 3, 4
                                               (AC)
         Rated Service Voltage, Ue                                 [V]  690         690              690                        690                  690                 690                  690                  690
                                               50-60Hz
         Rated Insulation Voltage, Ui                              [V]  800         1000             800                        1000                 1000                1000                 1000                 1000
         Rated Impulse Withstand Voltage, Uimp                    [kV]  8           8                8                          8                    8                   8                    8                    8
         Versions                                                      Fixed, Plug-in (1) Fixed, Withdraw-  Fixed, Plug-in      Fixed, Withdrawable,   Fixed, Withdrawable,   Fixed, Withdrawable  Fixed, Withdrawable  Fixed, Withdrawable
                                                                                    able, Plug-in                               Plug-in              Plug-in  (5)
         Breaking Capacities according to IEC 60947-2                  N            N       H        N                          N         H          N         H         S          H         S         H          S          H
         Rated Ultimate Short-Circuit Breaking Capacity, Icu
         Icu @ 220-230-240V 50-60Hz (AC)                          [kA]  65          65      100      50                         65        100        70        100       85         100       85        100        85         100
         Icu @ 415V 50-60Hz (AC)                                  [kA]  36          36      70       36                         36        70         36        70        50         70        50        70         50         70
         Icu @ 690V 50-60Hz (AC)                                  [kA]  6           10      15       5                          10        15         20        40        22         25        30        42         30         42
         Rated Service Short-Circuit Breaking Capacity, Ics
         Ics @ 220-230-240V 50-60Hz (AC)                          [kA]  75% (50)    100%    100%     75%                        100%      100%       100%      100%      100%       100%      100%      100%       100%       100%
         Ics @ 415V 50-60Hz (AC)                                  [kA]  100%        100%    100%     75%                        100%      100%       100%      100%      100%       100%      100%      100%       100%       100%
         Ics @ 690V 50-60Hz (AC)                                  [kA]  75% (5)     100%    100%     75%                        100%      100%       100%      100% (3)  100%       100%      100%      100%       100%       100%


         Utilization Category (IEC 60947-2)                            A            A                A                          A                    A (up to 630A),     A (up to 1000A),     B                    B
                                                                                                                                                     B (up to 500A)  (4)  B (up to 800A)  (4)
         Icw                                                      [kA]  -           -                -                          -                    6                   10                   20                   20
         Reference Standard                                            IEC 60947-2  IEC 60947-2      IEC 60947-2                IEC 60947-2          IEC 60947-2         IEC 60947-2          IEC 60947-2          IEC 60947-2
         Insulation Behaviour                                                                                                                                                                               
         Mounted on DIN rail                                           DIN EN 50022  DIN EN 50022    DIN EN 50022               DIN EN 50022         -                   -                    -                    -
                                                        [No. Operations]  25,000    25,000           25,000                     25,000               20,000              20,000               10,000               20,000
         Mechanical Life
                                                    [No. Hourly operations] 240     240              240                        240                  120                 120                  60                   60
                                                                                                                                                     7.000 (400A) - 5.000
                                                        [No. Operations]  8,000     8,000            8,000                      8,000                                    5,000                3,000                3,000
         Electrical Life @ 415 V (AC)                                                                                                                (630A)
                                                    [No. Hourly operations] 120     120              120                        120                  60                  60                   60                   60
         Dimensions
         Fixed                                 3 poles           [mm]  76.2 x 70 x 130  90 x 82.5 x 130  105 x 70 x 150         105 x 82.5 x 160     140 x 103 x 205     210 x 103.5 x 268    210 x 166 x 268      210 x 178 x 268
         (Width x Depth x Height)              4 poles           [mm] 101.6 x 70 x 130  120 x 82.5 x 130  140 x 70 x 150        140 x 82.5 x 160     186 x 103 x 205     280 x 103.5 x 268    280 x 166 x 268      280 x 178 x 268
         Trip units for power distribution
         TMD/TMA                                                                                                                                                      
         TMD/TMF                                                                                    
         Ekip Dip                                                                                                                                                                                             
         Trip units for motor protection
         MF/MA                                                                                                                                    
         Ekip Dip                                                                                                                                                                                             
         Ekip Touch                                                                                                                                                                                            
         Interchangeable trip units                                                                                                                                                                           
         Weight
         Fixed                                 3/4 poles          [kg]  1.1 / 1.4   1.2 / 1.6        1.7 / 2.1                  2.5 / 3.5            3.25 / 4.15         9.5 / 12             9.7 / 12.5           11 / 14
         Plug In (EF terminals)                3/4 poles          [kg]  2.21 / 2.82  2.54 / 3.27     3.24 / 4.1                 4.19 / 5.52          5.15 / 6.65
         Withdrawable (EF terminals)           3/4 poles          [kg]              3.32 / 4.04                                 5 / 6.76             5.4 / 6.9           12.1 / 15.1          29.7 / 39.6          32 / 42.6

          (1)  XT1 plug-in In max = 125A
          - Higher kA (120, 150 & 200) available as indent



          46                                     1300 556 601  |  ipd.com.au  |  V17-R04
   41   42   43   44   45   46   47   48   49   50   51