Moulded Case Circuit Breakers (MCCB)











                                                                                                                    1


 Size  XT1  XT2  XT3  XT4     XT5                 XT6 (2)              XT7                  XT7M
 Rated Uninterrupted Current  [A]  160  160  250  160 / 250  400 / 630  800 / 1000  (6)  800/ 1000 / 1250 / 1600  800 / 1000 / 1250 / 1600
 Poles  [No.]  3, 4  3, 4  3, 4  3, 4  3, 4       3, 4                 3, 4                 3, 4
 (AC)
 Rated Service Voltage, Ue  [V]  690  690  690  690  690  690          690                  690
 50-60Hz
 Rated Insulation Voltage, Ui  [V]  800  1000  800  1000  1000  1000   1000                 1000
 Rated Impulse Withstand Voltage, Uimp  [kV]  8  8  8  8  8  8         8                    8
 Versions  Fixed, Plug-in (1) Fixed, Withdraw-  Fixed, Plug-in  Fixed, Withdrawable,   Fixed, Withdrawable,   Fixed, Withdrawable  Fixed, Withdrawable  Fixed, Withdrawable
 able, Plug-in  Plug-in       Plug-in  (5)
 Breaking Capacities according to IEC 60947-2  N  N  H  N  N  H  N  H  S  H  S   H          S          H
 Rated Ultimate Short-Circuit Breaking Capacity, Icu
 Icu @ 220-230-240V 50-60Hz (AC)  [kA]  65  65  100  50  65  100  70  100  85  100  85  100  85        100
 Icu @ 415V 50-60Hz (AC)  [kA]  36  36  70  36  36  70  36  70  50  70  50       70         50         70
 Icu @ 690V 50-60Hz (AC)  [kA]  6  10  15  5  10  15  20  40  22  25   30        42         30         42
 Rated Service Short-Circuit Breaking Capacity, Ics
 Ics @ 220-230-240V 50-60Hz (AC)  [kA]  75% (50)  100%  100%  75%  100%  100%  100%  100%  100%  100%  100%  100%  100%  100%
 Ics @ 415V 50-60Hz (AC)  [kA]  100%  100%  100%  75%  100%  100%  100%  100%  100%  100%  100%  100%  100%  100%
 Ics @ 690V 50-60Hz (AC)  [kA]  75% (5)  100%  100%  75%  100%  100%  100%  100% (3)  100%  100%  100%  100%  100%  100%


 Utilization Category (IEC 60947-2)  A  A  A  A  A (up to 630A),   A (up to 1000A),  B      B
                              B (up to 500A)  (4)  B (up to 800A)  (4)
 Icw  [kA]  -  -  -  -        6                   10                   20                   20
 Reference Standard  IEC 60947-2  IEC 60947-2  IEC 60947-2  IEC 60947-2  IEC 60947-2  IEC 60947-2  IEC 60947-2  IEC 60947-2
 Insulation Behaviour                                                                
 Mounted on DIN rail  DIN EN 50022  DIN EN 50022  DIN EN 50022  DIN EN 50022  -  -  -       -
 [No. Operations]  25,000  25,000  25,000  25,000  20,000  20,000      10,000               20,000
 Mechanical Life
 [No. Hourly operations] 240  240  240  240  120  120                  60                   60
                              7.000 (400A) - 5.000
 [No. Operations]  8,000  8,000  8,000  8,000     5,000                3,000                3,000
 Electrical Life @ 415 V (AC)  (630A)
 [No. Hourly operations] 120  120  120  120  60   60                   60                   60
 Dimensions
 Fixed  3 poles  [mm]  76.2 x 70 x 130  90 x 82.5 x 130  105 x 70 x 150  105 x 82.5 x 160  140 x 103 x 205  210 x 103.5 x 268  210 x 166 x 268  210 x 178 x 268
 (Width x Depth x Height)  4 poles  [mm] 101.6 x 70 x 130  120 x 82.5 x 130  140 x 70 x 150  140 x 82.5 x 160  186 x 103 x 205  280 x 103.5 x 268  280 x 166 x 268  280 x 178 x 268
 Trip units for power distribution
 TMD/TMA                                       
 TMD/TMF    
 Ekip Dip                                                                              
 Trip units for motor protection
 MF/MA                     
 Ekip Dip                                                                              
 Ekip Touch                                                                             
 Interchangeable trip units                                                            
 Weight
 Fixed  3/4 poles  [kg]  1.1 / 1.4  1.2 / 1.6   1.7 / 2.1  2.5 / 3.5  3.25 / 4.15  9.5 / 12  9.7 / 12.5  11 / 14
 Plug In (EF terminals)  3/4 poles  [kg]  2.21 / 2.82  2.54 / 3.27   3.24 / 4.1  4.19 / 5.52  5.15 / 6.65
 Withdrawable (EF terminals)  3/4 poles  [kg]  3.32 / 4.04  5 / 6.76  5.4 / 6.9  12.1 / 15.1  29.7 / 39.6  32 / 42.6

        (2)  Not suitable for IT Distribution Systems  > 440V AC  (3)  Ics = 75% In > 500A  (4)  Category B: only when equipped with an electronic trip unit
        (5)  Plug-in/Withdrawable: max In 40°C = 600A
        (6)  1000A only for fixed execution with EF, ES, R and FCCuAl terminals. EF terminals are supplied as standard if no other terminals are ordered.

                                               1300 556 601  |  ipd.com.au  |  V17-R04                       47