Page 615 - IPD Product Catalog V17
P. 615
Motor Protection
MANUAL MOTOR STARTERS
THERMAL & ELECTROMAGNETIC PROTECTION - MS116
Features: Rated Short-circuit Rated
- No. of poles: 3 Operational Thermal Current Breaking Instantaneous
- Rotary handle operator Power AC-3 400V Setting Range Capacity 400V Short-circuit Part No.
(A)
- Compact and economic range (kW) AC - I (kA) Current - I (A)
cu
i
- Up to 15kW (400V) and 32A 0.03 0.10 - 0.16 100 2 MS116-0.16
- Built-in disconnect function 0.06 0.16 - 0.25 100 3 MS116-0.25
- Temperature compensation 0.09 0.25 - 0.40 100 5 MS116-0.4
- ON/OFF switch position with clear indication
0.18 0.40 - 0.63 100 8 MS116-0.63
0.25 0.63 - 1.00 100 13 MS116-1.0
0.55 1.00 - 1.60 100 20 MS116-1.6
0.75 1.60 - 2.50 75 31 MS116-2.5
1.5 2.50 - 4.00 75 50 MS116-4.0
2.2 4.00 - 6.30 50 79 MS116-6.3
4 6.30 - 10.0 50 150 MS116-10
5.5 8.00 - 12.0 50 180 MS116-12
7.5 10.0 - 16.0 16 240 MS116-16
7.5 16.0 - 20.0 16 300 MS116-20
MS116-16 11 20.0 - 25.0 16 375 MS116-25
15 25.0 - 32.0 16 480 MS116-32
- Manual motor starters should always be selected so that the actual motor current is within the
setting range. For full selection and technical details, please contact IPD.
4
THERMAL & ELECTROMAGNETIC PROTECTION - MS132
Features: Rated Short-circuit Rated
- No. of poles: 3 Operational Thermal Current Breaking Instantaneous
- Rotary handle operator Power AC-3 400V Setting Range Capacity 400V Short-circuit Part No.
- Compact and powerful range (kW) (A) AC - I (kA) Current - I (A)
i
cu
- Up to 15kW (400V) and 32A 0.03 0.10 - 0.16 100 2 MS132-0.16
- Built-in disconnect function 0.06 0.16 - 0.25 100 3 MS132-0.25
- Temperature compensation 0.09 0.25 - 0.40 100 5 MS132-0.4
- Lockable handle without accessories MS132-0.63
- ON/OFF/TRIP switch position with clear 0.18 0.40 - 0.63 100 8
indication 0.25 0.63 - 1.00 100 13 MS132-1.0
- Available with push-in spring terminals 0.55 1.00 - 1.60 100 20 MS132-1.6
0.75 1.60 - 2.50 100 31 MS132-2.5
1.5 2.50 - 4.00 100 50 MS132-4.0
2.2 4.00 - 6.30 100 79 MS132-6.3
4 6.30 - 10.0 100 150 MS132-10
5.5 8.00 - 12.0 100 180 MS132-12
7.5 10.0 - 16.0 100 240 MS132-16
7.5 16.0 - 20.0 100 300 MS132-20
11 20.0 - 25.0 50 375 MS132-25
15 25.0 - 32.0 50 480 MS132-32
MS132-10 - Manual motor starters should always be selected so that the actual motor current is within the
setting range. For full selection and technical details, please contact IPD.
1300 556 601 | ipd.com.au | V17-R05 615