Page 616 - IPD Product Catalog V17
P. 616
Motor Protection
MANUAL MOTOR STARTERS & ACCESSORIES
THERMAL & ELECTROMAGNETIC PROTECTION - MS165
Features: Rated Short-circuit Rated
- No. of poles: 3 Operational Thermal Current Breaking Instantaneous
- Rotary handle operator Power AC-3 400V Setting Range Capacity 400V Short-circuit Part No.
(A)
- Compact and powerful range (kW) AC - I (kA) Current - I (A)
i
cu
- Up to 45kW (400V) and 80A 7.5 10 - 16 100 240 MS165-16
- Built-in disconnect function 7.5 14 - 20 100 300 MS165-20
- Temperature compensation 11 18 - 25 100 375 MS165-25
- Lockable handle without accessories 15 23 - 32 100 480 MS165-32
- ON/OFF/TRIP switch position with clear
indication 22 30 - 42 50 630 MS165-42
22 40 - 54 50 810 MS165-54
30 52 - 65 50 975 MS165-65
37 62 - 73 30 1022 MS165-73
45 70 - 80 30 1120 MS165-80
- Manual motor starters should always be selected so that the actual motor current is within the
setting range. For full selection and technical details, please contact IPD.
ACCESSORIES
MS165-65
AUXILIARY CONTACTS - FRONT MOUNTING
Auxiliary Contacts
To Suit Part No.
NO NC
1 1 HKF1-11
MS116, MS132, MS165
2 0 HKF1-20
HKF1-11
AUXILIARY CONTACTS - RIGHT MOUNTING
Auxiliary Contacts
To Suit Part No.
NO NC
1 1 HK1-11
MS116, MS132, MS165 2 0 HK1-20
0 2 HK1-02
MS116, MS132 2 0 HK1-20L
HK1-11
SIGNALLING CONTACTS - RIGHT MOUNTING
Auxiliary Contacts
To Suit Description Part No.
NO NC
MS116, MS132, 1 1 For tripped alarm, with manual reset SK1-11
MS165 0 2 For tripped alarm, with manual reset SK1-02
1 1 For short-circuit alarm CK1-11
MS132, MS165 2 0 For short-circuit alarm CK1-20
0 2 For short-circuit alarm CK1-02
SK1-11 CK1-11
SHUNT TRIPS - LEFT MOUNTING
To Suit Rated Control Supply Voltage AC (V) Part No.
20 - 24 (50/60Hz) AA1-24
110 (50/60Hz) AA1-110
MS116, MS132, MS165
200 - 240 (50/60Hz) AA1-230
350 - 415 (50/60Hz) AA1-400
AA1-24
616 1300 556 601 | ipd.com.au | V17-R05