 Product range of the HVI  conductor.


 ®
 The prewired HVI  conductor I is equipped with a head piece  the conductor can be established on site. The components
 and an earth connection element at delivery. The earth  required for this (connection element with heat-shrinkable
 connection element is pre-mounted in its delivery condition.  sleeve and equipotential bonding element) are not fixed at
 ®
 ®
 Thus, the length of the HVI  conductor can be adjusted  delivery. This allows for adjusting the length of HVI  conductor
 ®
 (shortened) on site and the earth connection element can be  III on site. HVI  conductors II and III are used if e.g. several parts
 ®
 installed. HVI  conductor I is used e.g. when directly connecting  of a plant to be protected are not supposed to be connected
 the air-termination system to the earth-termination system of  individually but jointly to the earth-termination system of the
 the structure. An equipotential bonding element is firmly  structure via a separate ring conductor (consideration of the
 attached at the end of the sealing unit area for the connection  separation distance).
 ®
 of the HVI  conductor to the equipotential bonding (EB)
 ®
 structure.  The HVI  conductor can also be installed in the insulating pipe
 ®
 At delivery, the prewired HVI  conductor II is equipped with  at locations with special architectural requirements.
 two adjusted head pieces the length of which cannot be changed
 on site.
 ®
 The prewired HVI  conductor III is equipped with a fixed sealing
 unit consisting of a head piece and a fixed equipotential bonding
 element at delivery. An additional sealing unit at the end of
 Isolated air-termination systems for antennas and  Omnidirectional antennas
 emitting characteristics / omnidirectional antennas.















 e.g.  e.g.
 ®
 ®
 HVI  conductor I  HVI  conductor I
 in the insulating pipe  in the insulating pipe
 Part No. 819 320  Part No. 819 360
 L = 3200 mm  L = 3200 mm

 ®
 HVI  conductor
 ®
 HVI  conductor
 Antennas with 360° emitting characteristics (omnidirectional  Units:
 antennas) are used for different radio applications.  Hz  m
 When installing isolated air-termination systems for  Frequency [F]  Wave length [ ]
 omnidirectional antennas, it has to be considered that an isolated
 air-termination rod with a sufficient protective angle covers the  100 000  3000
 antenna to be protected. Furthermore it has to be ensured that  1 000 000  300
 sufficient separation distance is maintained.
 10 000 000  30
 From a functional point of view, a distance has to be kept  80 x 10 6  3.75
 between the antenna and the air-termination system, which  100 x 10 6  3
 corresponds to a quarter of the wave length of the radio  6
 frequency used. The installation conditions according to  160 x 10  1.875
 installation instructions No. 1521 have to be observed.  900 x 10 6  0.33
 1800 x 10 6  0.17
 Covered by DEHN distance holders for omnidirectional antennas.