Page 23 - Reliable_System_Solutions
P. 23

No proximities with DEHNcon-H.


 Metal and electric superstructures protruding above the roof  The equivalent separation distance of the newly developed
 are particularly exposed lightning striking points. If the external  HVI conductor light is s ≤ 0.45 m (in air) or s ≤ 0.90 m (solid
 lightning protection system is installed correctly, that is with  material).
 an isolated air-termination system for these roof superstructures,
 partial lightning currents are not induced into the building.  DEHNcon-H comes with a practice-oriented design since the
 dimensions of the insulating pipes were reduced. Another
 The new lightning protection standard DIN EN 62305-3 (VDE  benefit of DEHNcon-H is the reduced weight of the total
 0185-305-3), the safety standard for antenna installations DIN  structure. This allows for already existing antenna masts to
 EN 60728-11 (VDE 0855-1) as well as the supplementary sheet  be retrofitted with DEHNcon-H.
 1 of DIN VDE 0845 for surge protection of IT systems call for
 an isolated lightning protection system or an isolated air-  Possible applications are protection against direct lightning
 termination system for antenna installations or other  strokes into:
 installations protruding above the roof.
 Antennas (satellite antennas, terrestrial antennas, DVBT
 DEHN + SÖHNE added another application to the tried and  receiver installations)
 tested DEHNconductor system: DEHNcon-H  Photovoltaic and solar thermal systems
 The variable component system consists of the following  Object surveillance systems
 components:  Our condensed catalogue P2, which is valid as from 1st January
 ®
 HVI  conductor light, a refined insulated down conductor,  2008, contains a comprehensive component overview. For
 which is installed in an insulating pipe with air-termination  more detailed information on DEHNcon-H please refer to  DEHNcon-H
 tip  installation instructions No. 1632.
 Fixing elements, conductor holders and other accessories  Fixing clamp
 made of StSt (V2A)
 Roof conductor holder  Part No. 105 161
 height 175 mm
 Part No. 202 836
 Roof conductor holder
 height 75 mm
 Part No. 202 831









  light
 ®
 HVI











 d=0





 l = 90 cm




 r ≥ 17.5 cm
   18   19   20   21   22   23   24   25   26   27   28