Page 3 - 12_DS164_E_0413_Blitzductor_XTU
P. 3
INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR XTU
®
PLUGGABLE SPDS FOR DIN RAIL MOUNTING Universal lightning current /
surge arrester
• Combined lightning current and surge arrester
– Capable of carrying lightning currents up to 10 kA
(10/350 µs)
– Low voltage protection level, also suited for the
protection of terminal equipment
– For use in conformity with the lightning protec-
tion zones concept at the boundaries from 0 A – 2
and higher
• SPD consists of a protection module and base
part
– Easy replacement of protection modules
– Make-before-break switch contact in the base
part allows removal and insertion without inter-
ruption
• With integrated LifeCheck monitoring function
Testing of an SPD module via RFID technology (LifeCheck) – SPDs can be tested without downtime
– Even detects previously damaged arresters
BLITZDUCTOR XTU arresters are pluggable, multipole and universal DIN
rail mounted lightning current and surge arresters for the protection of
measuring and control circuits, bus systems and telecommunication sys-
tems in which high levels of availability are essential. For effective pro- 2'4' 1'3'
tection of terminal equipment against lightning effects and surges, BLITZ-
DUCTOR XTU arresters combine the permanently high impulse current
2 4
discharge capacity of a lightning current arrester with the low voltage
protection level of a surge arrester which is optimally adjusted to the 1 3
operating voltage currently applied.
LifeCheck allows easy and fast testing of SPDs without removing the
module from the system circuit. Integrated into the SPD modules,
LifeCheck permanently monitors the proper condition of the SPD and acts
like an early warning system, detecting electrical or thermal overload of Up to four lines can be connected on two levels. For DIN rail mounting
the protection components.The LifeCheck status can be read out within a purposes, lines of a pair belonging to each other are connected on top of
matter of seconds via contactless RFID technology by means of the one another.
portable DEHNrecord LC reader and shows the date of the last test of the
SPD module.
Stationary installed, a condition monitoring system allows condition-
based maintenance of 10 BXT arresters (for more detailed information, LifeCheck module
please refer to page 6). BXTU ML2 ... S ...
2 2’
The module locking mechanism ensures safe operation, thus the arrester 4 4’
provides protection against vibration effects and shock loads up to a 30-
fold acceleration of gravity. The function-optimised design of the arrester 12 3 4 4´ 3´ 2´ 1´
ensures both fast and easy replacement of the arrester module which 1 3 1’
houses all relevant protection elements. 3’
Base part
BXT BAS 9
A wide range of accessories makes the BLITZDUCTOR XTU arrester partic-
ularly user-friendly. Elements for labelling, earthing of unused lines or If the line shield cannot be directly earthed on both sides for technical rea-
easy testing of lines complete the product range. sons, one-sided indirect shield earthing might be advisable. This can be
performed by using arrester modules of type BXTU ML2 ... S. The terminal
3, 3’ is connected to a gas discharge tube which is capable of carrying
lightning currents and prevents compensating currents. Transient impulse
currents on the shield are discharged via indirect shield earthing.
www.dehn.de 3