           PLUGGABLE SPDS FOR DIN RAIL MOUNTING                                                       Diagrams



                                                         250 V
               U
                                                            Up
                   Operating voltage U N
                                                                                                               C2
                                                         200 V
                                                                                                               C3
                                                                                                               U N
                                         U Signal
                                                         150 V
                 U N
                                                         100 V
                                             t [time]
                                                                                         Up   line-line for In (8/20 µs) C2
           Operating voltage U N and superimposed signal voltage  50 V
                                                                                         Up   line-line for 1 kV/µs C3
           U Signal
                                                                                                             UN
                                                           0 V   20 V  40 V  60 V  80 V  100 V  120 V  140 V  160 V  180 V
                                                                               Operating voltage U N

                                                             Voltage protection level U p as a function of the operating voltage U N

                                                                                                ®
                                                                              BLITZDUCTOR XT Base Part
   920 300  BXT BAS
                                                                                                        BXT BAS


   BXT BAS
   920 300                                               2           2´
                                                         4           4´
                                                   BXT BAS              protected
                                                             2
                                                                 3´
                                                             13 4  4´ 2´1´
                                                        1             1´
                                                        3             3´
                                                   BXT ML4...
                                                         2           2´  protected
                                                         4           4´
                                                   BXT BAS  12 3 4  4´ 3´  2´ 1´
                                                        1             1´
                                                        3             3´
                  Dimension drawing BXT BAS      Basic circuit diagram with and without plug-in  • Four-pole version for universal use
                                                             module                  with all types of SPD modules
           The BLITZDUCTOR XT base part is a very space-saving, four-pole, universal feed-through terminal  • The modules can be plugged in and
           for the insertion of SPD modules without signal interruption. The snap-in mechanism at the sup-  removed without signal interruption
           porting foot of the base part allows the device to be safely earthed via the  DIN rail. As no compo-  • Universal design without protection
           nents of the protective circuit are situated in the base part, maintenance operation is only required  elements
           for the protection modules.

                                                            BXT BAS
            Operating temperature range                    -40°C...+80°C
            Degree of protection                             IP 20
            For mounting on                           35 mm DIN rail acc. to EN 60715
            Connection type input / output                 screw / screw
            Cross-sectional area, solid                    0.08 - 4 mm 2
            Cross-sectional area, flexible                 0.08 - 2.5 mm 2
            Tightening torque (terminals)                    0.4 Nm
            Earthing via                              35 mm DIN rail acc. to EN 60715
            Enclosure material                            polyamide PA 6.6
            Colour                                           yellow
            Ex certifications *)                  ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
                                                     IECEx KEM 09.0053X: Ex nA II T4 Gc
            Approvals, Certifications                    CSA, VdS, UL, GOST
            Ordering information
            Type                                            BXT BAS
            Part No.                                        920 300
            Packing unit                                     1 pc(s).
           *) In combination with certified module

    www.dehn.de                                                                                                   5
   1   2   3   4   5   6   7   8