Page 4 - 12_DS164_E_0413_Blitzductor_XTU
P. 4

BLITZDUCTOR XTU LifeCheck -Modules                    INFORMATION TECHNOLOGY SYSTEMS
                        ®
                                             ®
                                                                                                                920 300  BXT BAS
       BXTU ML4 BD 0-180 /                            PLUGGABLE SPDS FOR DIN RAIL MOUNTING
       BXTU ML2 BD S 0-180

                                             1                      1‘            1                      1‘     BXT BAS 920 300
       NEW                                           i  U>U N                             i  U>U N
                                             2                      2‘            2                      2‘
                                                     i                                    i
                                            9                      protected     9                      protected
                                             3                      3‘
                                                     i
                                                        U>U N
                                                                                  3                      3‘
                                             4                      4‘            4                      4‘
                                                     i
       • Universal voltage type with         Basic circuit diagram BXTU ML4 BD 0-180  Basic circuit diagram BXTU ML2 BD S 0-180
        actiVsense technology
       • For installation in compliance with  Space-saving combined SPD module with actiVsense and LifeCheck technology for protecting lines
        the lightning protection zones con-  of balanced interfaces which are galvanically isolated.
        cept at all boundaries from 0 A – 2 or  BXTU ML4 BD 0-180: for even with different operating voltages isolated pairs
        higher                             BXTU ML2 BD S 0-180: for one pair, with direct or indirect shield earthing
       • With integrated LifeCheck monitoring  Automatically detects the operating voltage of the wanted signal and optimally adjusts the volt-
        function                           age protection level to the operating voltage currently applied.


                                                   BXTU ML4 BD 0-180                   BXTU ML2 BD S 0-180
       SPD class                                       M                                   M
       SPD monitoring system                            LifeCheck                           LifeCheck
       Operating voltage U N                            0 - 180 V                           0 - 180 V
       Frequency of the operating voltage f UN          ≤ 400 Hz                            ≤ 400 Hz
       Max. continuous operating d.c. voltage U C        180 V                               180 V
       Max. continuous operating a.c. voltage U C        127 V                               127 V
       Permissible superimposed signal voltage U Signal  ≤ +/- 5 V                          ≤ +/- 5 V
       Cut-off frequency line-line (U signal, balanced 100 ohms) f G  25 MHz                25 MHz
       Nominal current at 80° C I L                     100 mA                              100 mA
       D1 Total lightning impulse current (10/350 µs) I imp  10 kA                           9 kA
       D1 Lightning impulse current (10/350 µs) per line I imp  2.5 kA                       2.5 kA
       C2 Total nominal discharge current (8/20 µs) I n  20 kA                               20 kA
       C2 Nominal discharge current (8/20 µs) per line I n  10 kA                            10 kA
       Voltage protection level line-line for I n C2 U p  see diagram, line C2           see diagram, line C2
       Voltage protection level line-line at 1 kV/µs C3 U p  see diagram, line C3        see diagram, line C3
       Voltage protection level line-line for I imp D1 U p  ≤ U N + 53 V                   ≤ U N + 53 V
       Voltage protection level line-PG for C2/C3/D1    ≤ 550 V                              ≤ 550 V
       Series impedance per line R                ≤ 10 ohms; typically 7.5 ohms       ≤ 10 ohms; typically 7.5 ohms
       Capacitance line-line C                          ≤ 200 pF                            ≤ 200 pF
       Capacitance line-PG C                            ≤ 16 pF                              ≤ 25 pF
       Operating temperature range                    -40°C...+80°C                        -40°C...+80°C
       Degree of protection (SPD plugged-in)             IP 20                               IP 20
       Pluggable into                                BXT BAS base part                   BXT BAS base part
       Earthing via                                  BXT BAS base part                   BXT BAS base part
       Enclosure material                            polyamide PA 6.6                     polyamide PA 6.6
       Colour                                           yellow                               yellow
       Test standards                                  EN 61643-21                         EN 61643-21
       Approvals, Certifications                         GOST                                GOST
       Ordering information
       Type                                          BXTU ML4 BD 0-180                  BXTU ML2 BD S 0-180
       Part No.                                         920 349                             920 249
       Packing unit                                     1 pc(s).                             1 pc(s).





                                           • Dimension drawing of BLITZDUCTOR XT
                                             base part with plugged-in arrester
                                             module
                                           • Width: 2/3 modules (12 mm), suitable
                                             for DIN rail mounting in distribution
                                             boards


       4                                                                                                       www.dehn.de