Page 58 - Arc Guard System - TVOC-2
P. 58

58               ABB  ARC GUARD SYSTEM™ – TVOC-2  INSTALLATION AND MAINTENANCE GUIDE




         8.1     Technical data


         Table 1  Technical data
         Common technical data       Overvoltage category        III
                                     Pollution degreee           3
         Power supply                Rated operation voltage Ue  TvOC-2-240: 100 - 250 v DC  TvOC-2-48: 24 - 48 v DC
                                                                 100 - 240 v AC 50-60 HZ  Possibility to connect
                                                                                         two power supplies for
                                                                                         redundancy. (Common minus)
                                     Rared insulation voltage Ui  250 v with reinforced insulation
                                     Rated impulse withstand voltage   4 kv
                                     Uimp
         Output contacts             Terminals   Description     U i          U e                    U imp
                                     11, 12, 14  IRF signal      250 v        250 v AC 50-60 HZ, 250 v DC  4 kv
         Contact rated voltage with
         reinforced insulation between   21, 22, 23  Signal relay  250 v      250 v AC 50-60 HZ, 250 v DC  4 kv
         different contacts          31, 32, 34  Signal relay    250 v        250 v AC 50-60 HZ, 250 v DC  4 kv
                                     43, 44      Trip contact    250 v        250 v AC 50-60 HZ, 250 v DC  4 kv
                                     53, 54      Trip contact    250 v        250 v AC 50-60 HZ, 250 v DC  4 kv
                                     63, 64      Trip contact    250 v        250 v AC 50-60 HZ, 250 v DC  4 kv
                                     73, 74      50 v            50 v DC      0.5 kv
         Environmental specifications  Permissible ambient temperature in   - 25 to + 55 °C
                                     operation
                                     Permissible ambient temperature in   - 25 to + 70°C
                                     transportation and storage
                                     Humidity                    Maximum 95%
                                     Altitude                    Less than 2000m above sea level.
                                     Degree of protection        IP20 Arc Monitor
                                                                 IP54 HMI front side
         Safety parameters for application   Life time           10 years
         according to IEC61508                                          -03
                                     PFD                         3.49 x 10
         Optical inputs and outputs  Optical detectors           10 inputs (without extensions)
                                     Current signal from CSU-2   2 inputs X21, X22 (optical)
                                     Forward current signal to another Arc   1 output: X1.23 (optical)
                                     Monitor
         Trip contacts (K4, K5, K6)  Solid state contacts        3 NO solid state type IGBT
                                     Rated voltage 250 v AC/DC   250 v AC/DC
                                     Make and carry for 0.2 s    30 A
                                     Make and carry for 1 s 0.15% duty ration  10 A
                                     Breaking capacity           250 v       1.5 A       AC - 15
                                                                 250 v       1 A         DC - 13
   08
                                                                 110 v       3 A         DC - 13
                                                                 48 v        3 A         DC - 13
                                                                 Reinforced insulation between separate contacts.
                                                                 voltage drop 5 v 30 A, 3 v 3 A, 2 v 10 mA
                                                                 Off state current < 1 mA at 250 v
                                                                 Min. recommended load current 10 mA
         Signal relay (K2, K3)       Manual or auto resetable    2 CO gold-plated contacts
                                     Rated voltage               250 v AC/DC
                                     Continous carry I th        5 A
                                     Make and carry for 0,2 s    30 A
                                     Make and carry for 3 s 10% duty ratio  15 A
                                     Breaking capacity           250 v       3 A         AC - 15
                                                                 250 v       0,3 A       DC - 13
                                                                 110 v       0,6 A       DC - 13
                                                                 48 v        2 A         DC - 13
                                                                 Reinforced insulation between separate contacts
                                                                 I  = 5 A
                                                                  th
                                                                 Min switching load:
                                                                 1 mA at 5 v DC with contacts not used for switching current
                                                                 > 0.5 A if inductive/capacitive load before.
   53   54   55   56   57   58   59   60   61   62   63