ABB  ARC GUARD SYSTEM™ – TVOC-2  INSTALLATION AND MAINTENANCE GUIDE                59







          Table 1  Technical data
          Internal Relay Fault (IRF, K1)  Self supervision alarm relay  1 CO gold-plated contact
                                     Rated voltage               250 v AC/DC
                                     Continous carry I th        5 A
                                     Make and carry for 3 s      8 A
                                     Breaking capacity           250 v       1,5 A       AC - 15
                                                                 250 v       0,15 A      DC - 13
                                                                 110 v       0,3 A       DC - 13
                                                                 48 v        0,5 A       DC - 13
                                                                 Reinforced insulation between separate contacts.
                                                                 I  = 5 A
                                                                  th
                                                                 Min switching load:
                                                                 1 mA at 5 v DC with contacts not used for switching current
                                                                 > 0.5 A if inductive/capacitive load before.
          Settings and indications   Connections for HMI on Arc Monitor  1 output RJ45 male at front side
                                                                 1 output RJ14 female at the right side)
                                     Display on HMI              52 x 26 mm graphic LCD with LED backlight
                                     Keyboard on HMI             Membrane buttons, 4 soft key
                                     LED signal on HMI           Power, Trip, Error
                                     LED signal on Arc Monitor and   Power, Trip
                                     extension module
                                     Configuration switches      8 - pole DIP switch on Arc Monitor front
                                     Settings (HMI)              Time and display language
                                     Configuration (DIP switches)  Manual or auto reset of K2 and K3
                                                                 Use of CSU-2 or not trip configuration
                                     Display information         Trip log, connected modules, actual configuration self
                                                                 diagnostic test result and error log
          Power supply                                           TVOC-2-240              TVOC-2-48
                                     Rated supply voltage,U s    100-240 v AC 50-60 Hz   24 - 48 v DC Possibility to
                                                                 100-250 v DC            connect two power supplies
                                                                                         for redundancy. (Common
                                                                                         minus)
                                     U variation                 AC - 20% - +10%         DC -25% - +30%
                                      s
                                                                 DC - 25% - + 30%
                                     Rated insulation voltage, U s  250 v with reinforced insulation  250 v with reinforced
                                                                                         insulation
                                     Rated impulse withstand voltage U s  4 kv           4 kv

                                     Main MCB/fuse               Max. 10 A char. C/fuse 10 A gG  Max 6A, MCB ABB Type S202
                                                                                         Z6A
                                                                                                                      08
                                     Power consumption           5 W                     5W
          Start-up time              Trip possible               < 15 ms from power on   < 100 ms from power on
          Reaction time              From light detection to trip contacts (   Approx. 1ms (depends on light intensity)
                                     K4, K5 ,K6)
                                     From light detection to trip signal   < 10 ms
                                     relays (K2, K3)
                                     Current condition from input to   <0,4 ms
                                     output
          Detector                   Maximum length              30 m with AM and extension - E1 , E6-S
                                                                 60 m with extension - E3
                                     Service temperature range   - 25 to + 70 °C continous
                                                                 - 25 to + 85 °C short-time
                                     Smallest permissible bending radius  35 mm after installation
                                                                 20 mm on handling
                                     Acceptable backlight intensity light   3000 Lux
                                     without tripping
          Optical cable for connecting CSU-2   Maximum length    30 m