ABB TRANSFER AND CHANGE-OVER SWITCHES 83
—
Motorized change-over switches
Motor operator performance data for OTM160…3200_C
Switch size 160…250 315...400 630…800 1000…1600 2000…3200
Data according to IEC 60947
Rated operational voltage U e Pollution degree 3 V AC 220 - 240
50/60 Hz V AC/DC 110 - 125
V DC 48
V DC 24
Operating voltage range 0.85 - 1.1 x U e 03
Operating time 1) 90° I-0, 0-I, 0-II, II-0 220-240VAC s 0.4-1.0 0.4-1.0 0.4-1.0 0.5-1.5 0.5-1.5
110-125VAC/DC s 0.5-1.5 0.5-1.5 0.6-1.2 0.5-1.5 0.5-1.5
48VDC s 0.5-1.5 0.4-1.0 0.6-1.6 0.5-1.5 0.5-1.5
24VDC s 0.4-1.0 0.4-1.0 0.5-1.5 1.0-2.0 1.0-2.0
Operating transfer time 1) 180° I-0-II, II-0-I 220-240VAC s 1.0-2.0 0.9-2.0 0.9-2.0 1.5-3.0 1.5-3.0
110-125VAC/DC s 1.1-2.5 1.2-2.6 1.2-3.0 1.5-3.0 1.5-3.0
48VDC s 1.4-2.5 1.0-2.0 1.3-3.0 1.5-3.0 1.5-3.0
24VDC s 1.0-2.0 1.0-2.0 1.1-2.5 2.0-3.5 2.0-3.5
OFF -time when operating I-II or II-I 1) 180° I-II, II-I 220-240VAC s 0.4-1.0 0.4-1.0 0.4-1.0 0.5-1.5 0.5-1.5
110-125VAC/DC s 0.4-1.1 0.5-1.5 0.6-1.5 0.5-1.5 0.5-1.5
48VDC s 0.5-1.1 0.4-1.0 0.7-1.6 0.5-1.5 0.5-1.5
24VDC s 0.4-1.0 0.4-1.0 0.5-1.5 0.8-1.7 0.8-1.7
Nominal current In 1) 220-240VAC A 0.2 0.5 0.7 1.8 1.8
110-125VAC/DC A 0.5 0.6 0.8 3.0 3.0
48VDC A 1.1 2.1 2.6 5.3 5.3
24VDC A 3.3 4.2 4 8.0 8.0
Current inrush 1) 220-240VAC A 1.3 2.1 2.8 7.7 7.7
110-125VAC/DC A 2.1 2.5 4.6 13.3 13.3
48VDC A 4.4 8.3 8.4 22.4 22.4
24VDC A 16.8 17.5 22.4 26.6 26.6
Overload fuse Type / In / Capacity 220-240VAC mA T/315/H T/500/H T/1 000/H T/2 000/H T/2 000/H
110-125VAC/DC mA T/500/H T/630/H T/1 000/H T/4 000/H T/4 000/H
48VDC A T/1.25/H T/2.5/H T/2.5/H T/5/H T/5/H
24VDC A T/4.0/H T/5.0/H T/5.0/H T/10/H T/10/H
Size mm 5x20 5x20 5x20 5x20 5x20
Operating rate Cycle 0-I-0-II-0, 220-240VAC cycles/min 1 1 1 0.5 0.5
max. continuous 110-125VAC/DC cycles/min 1 1 1 0.5 0.5
48VDC cycles/min 1 1 1 0.5 0.5
24VDC cycles/min 1 1 1 0.5 0.5
Max. short-time, 220-240VAC cycles/min 10 10 10 5 5
≤ 10 cycles 110-125VAC/DC cycles/min 10 10 10 5 5
48VDC cycles/min 10 10 10 5 5
24VDC cycles/min 10 10 10 5 5
Overvoltage category III
Rated impulse withstand voltage U imp kV 4
Dielectric strength 50 Hz 1 min. kV 1.5
Impulse command Min. impulse ms 100
duration
Terminals
PE - N - L
Voltage supply wiring for U e
Cross section solid/stranded mm² 1.5 - 2.5
Short-circuit protection device max. MCB A C16
Control terminal (no SELV) C - II - I - O
Cross section solid/stranded mm² 1.5 - 2.5
Maximum cable length m 100
State information of locking (no SELV)
Handle attached or motor operator 11-12-14 (C/O) 5A/250V/cosΦ=1
locked
Locking motor operator 23-24 (NO) 5A/250V/cosΦ=1
Short-circuit protection device Max. MCB A C2
Protection degree IP20
Operating temperature °C -25…+55
Transportation and storage temperature °C -40…+70
Max. altitude m 2 000
1) Under nominal conditions