ABB  TRANSFER AND CHANGE-OVER SWITCHES                                             81




          —
          Motorized change-over switches


          Technical data for OTM1000...3200 _C


          Switch size                                             OT_1000_  OT_1250_  OT_1600_  OT_2000_ OT_2500_ OT_3200_
          Data according to IEC 60947-3
          Rated insulation voltage and rated     Pollution degree 3  2) V  1 000  1 000  1 000  1 000  1 000  1 000
          operational voltage AC20/DC20  1)
          Dielectric strength                    50 Hz 1min.  kV   10      10       10      10     10     10
          Rated impulse withstand voltage  3)                kV    12      12       12      12     12     12
          Rated thermal current and rated    / ambient 40°C   In open air   A  1 000  1 250  1 600  2 000  2 500  3 200  03
          operational current AC20/DC20  / ambient 40°C   In enclosure  A
          ..with minimum conductor
          cross section                          Cu          mm²   2x300   2x400    2x500   3x500  4x500  4x1 000
          Rated operational current, AC-21A      up to 500 V  A    1 000   1 250    1 600   2 000  5)  2 500  5)  3 200  5)
                                                 690 V       A     1 000   1 250    1 600
          Rated operational current, AC-22A      up to 500 V  A    1 000   1 250    1 600
                                                  690 V      A     1 000   1 250    1 600
          Rated operational current, AC-23A      up to 500 V  A    1 000   1 250    1 250
                                                 690 V       A     1 000   1 250    1 250
          Rated operational power, AC-23A  1)    230 V       kW    315     400      400
          The kW-ratings are accurate for        415 V       kW    560     710      710
          3-phase 1500 R.P.M. standard
          asychronous motors                     500 V       kW    710     900      900
                                                 690 V       kW    1 000   1 200    1 200
          Rated breaking capacity                up to 415 V  A    10 000  10 000   10 000
          in category AC-23                      500 V       A     10 000  10 000   10 000
                                                 690 V       A     10 000  10 000   10 000
          Rated conditional short-circuit    I p (r.m.s.) 80 kA, 415 V  îc (peak)  kA  100  100  100
          current I p (r.m.s.) and cut-off    Max. OFA_ fuse size   gG/aM  A/A  1 250/1 250  1 250/1 250  1 250/1 250
          current î c (peak) value. The cut-off
          current î c refers to values listed by   I p (r.m.s.) 100 kA, 500 V  îc (peak)  kA  106  106  106
          fuse manufacturers (single phase    Max. OFA_ fuse size   gG/aM  A  1 250/1 250  1 250/1 250  1 250/1 250
          test acc. to IEC60269).  I p (r.m.s.) 80 kA, 690 V  îc (peak)  kA
                                Max. OFA_ fuse size   gG/aM  A
          Rated short-time withstand current  I cw (r.m.s.)  690 V 0.15s  kA  50  50  50    50     50
                                                 690 V 0.25s  kA   50      50       50      50     50
                                                 690 V 1s    kA    50      50       50      55     55     65
          Rated short-time making capacity  2)  I cm (peak)  3)  690 V  kA  92  92  92      110    110    143
          Power loss / pole     With rated current           W     19      29       48      55     85     95
          Mechanical endurance  Number of oper. cycles  4)   Cycles  3 000  3 000   3 000   2 000  2 000  2 000
          Terminal bolt size    Metric thread diameter       mm    M12x60  M12x60   M12x60  M12x60  M12x60  M12x100
                                 x length
          Terminal tightening torque  Counter torque required  Nm  50-75   50-75    50-75   50-75  50-75  50-75
          Operating torque      3-pole change-over           Nm    78      78       78      78     78     80
                                switches
          Weight without accessories  3-pole switch          kg    42      42       44      56     56     83
                                4-pole switch                kg    50      50       52      70     70     101
          Data according to IEC 60947-6-1
          Class of equipment                                       PC      PC       PC
          Rated short-time withstand current  I cw (r.m.s.)  690 V 0.1s  kA  50  50  50
          Rated operational current, AC-31B      up to 415 V  A    1 000   1 250    1 600
          Rated operational current, AC-33B      up to 415 V  A    1 000   1 000    1 000
          1)  These values are given for guidance and may vary acc. to the motor manufacturer
          2)  Short circuit duration > 50ms, without fuse protection
          3)  Max. distance from switch frame to nearest busbar / cable support 150 mm
          4)  Operating cycle: O - I - O - II - O
          5)  Category AC-21B, up to 415V