Page 79 - Changeover switch
P. 79

ABB  TRANSFER AND CHANGE-OVER SWITCHES                                             79




          —
          Motorized change-over switches

          Technical data for OTM16...125_C



          Switch size                                                    OTM40_    OTM63_  OTM80_  OTM100_  OTM125_
          Data according to IEC 60947-3
          Rated insulation voltage and rated              Pollution   V  800       800    800     800    800
          operational voltage AC20/DC20                   degree 3
          Dielectric strength                             50 Hz 1min.  kV  6       6      6       6      6
          Rated impulse withstand voltage                          kV    8         8      8       8      8
          Rated thermal current and rated    / ambient 40°C   In open air   A  40  63     80      115    125
          operational current AC20/DC20    / ambient 40°C   In enclosure  A  40    63     80      115    125           03
          ..with minimum conductor cross section
                                           / ambient 60°C  In enclosure  A  32     50     63      80     100
                                                          Cu       mm²   10        16     25      35     50
          Rated operational current, AC-21A               up to 500 V  A  40       63     80      100    125
                                                          690 V    A     40        63     80      100    125
          Rated operational current, AC-22A               up to 500 V  A  40       63     80      100    125
                                                           690 V   A     40        63     80      100    125
          Rated operational current, AC-23A               up to 415 V  A  40       63     80      80     90
                                                          500 V    A     40        60     60      60     70
                                                          690 V    A     40        40     40      40     50
          Rated operational current / poles in series, DC-21A  up to 48 V  A   40/1  63/1  80/1   100/1  125/1
                                                          110 V    A     40/2      63/2   80/2    100/2  125/2
                                                          220 V    A     40/4      63/4   80/4    100/4  100/4
          Rated operational current / poles in series, DC-22A  up to 48 V  A  40/1  63/1  80/1    100/1  125/1
                                                          110 V    A     40/2      63/2   80/2    100/2  125/2
                                                          220 V    A     40/4      63/4   80/4    80/4   80/4
          Rated operational current / poles in series, DC-23A  up to 48 V  A  40/1  63/1  80/1    100/1  125/1
                                                          110 V    A     40/2      63/2   80/2    100/2  125/2
                                                          220 V    A     40/4      63/4   63/4    63/4   63/4
          Rated operational power, AC-23A  1)             230 V    kW    7.5       15     22      22     22
          The kW-ratings are accurate for 3-phase 1500 R.P.M.   415 V  kW  18.5    30     37      37     45
          standard asychronous motors
                                                          500 V    kW    22        37     37      37     45
                                                          690 V    kW    37        37     37      37     45
          Rated breaking capacity in category AC-23       up to 415 V  A  320      504    640     640    720
                                                          500 V    A     320       480    480     480    560
                                                          690 V    A     320       320    320     320    400
          Rated conditional short-circuit current I p (r.m.s.)    Ip (r.m.s.) 50 kA, 415 V  îc (peak)  kA  16.5  16.5  16.5  16.5  16.5
          and corresponding max. allowed cut-off current î c    Max. OFA_ fuse size   gG/aM  A/A  125/125  125/125  125/125  125/125  125/125
          (peak) value. The cut-off current î c refers to values
          listed by fuse manufacturers (single phase test    Ip (r.m.s.) 18 kA, 690 V  îc (peak)  kA  11  11  11  11  11
          acc. to IEC60269).               Max. OFA_ fuse size  gG  A    125       125    125     125    125
                                           Ip (r.m.s.) 50 kA, 690 V  îc (peak)  kA  10  10  10    10     10
                                           Max. OFA_ fuse size  gG/aM  A/A  63/63  63/63  63/63   63/63  63/63
          Rated short-time withstand current  I cw (r.m.s.)  690 V 1s  kA  2.5     2.5    2.5     2.5    2.5
          Rated short-time making capacity  2)  I cm (peak)  690 V  kA   3.6       3.6    3.6     3.6    3.6
          Power loss / pole                With rated current      W     1.6       2.8    3.5     4.0    6.3
          Mechanical endurance             Number of oper. cycles  3)  Cycles  10 000  10 000  10 000  10 000  10 000
          Cable size                       Cu-wire size suitable for  mm²  2.5-25/2x2.5-16  10-70  10-70  10-70  10-70
                                           terminal clamps         AWG   14-4/2x14-6  8-00  8-00  8-00   8-00
          Terminal tightening torque       Counter torque required  Nm   6         6      6       6      6
          Operating torque                 3-pole switches         Nm    5         5      5       5      5
          Weight without accessories       3-pole switch           kg    1.37      1.37   1.37    1.37   1.37
                                           4-pole switch           kg    1.60      1.60   1.60    1.60   1.60
          Data according to IEC 60947-6-1
          Class of equipment                                             PC        PC     PC      PC     PC
          Rated short-time withstand current  I cw (r.m.s.)  690 V 0.1s  kA  5     5      5       5      5
          Conditional short-circuit current  I cc (r.m.s.)  415 V  kA    50        50     50      50     50
          Corresponding fuse rating        gG/aM fuse     415 V    A     125       125    125     125    125
          Rated operational current, AC-31B               up to 415 V  A  40       63     80      100    125
          Rated operational current, AC-32B               up to 415 V  A  40       63     80      100    125
          Rated operational current, AC-33B               up to 415 V  A  40       63     80      80     80
          1)  These values are given for guidance and may vary according to the motor manufacturer
          2)  Short circuit duration > 50ms, without fuse protection
          3)  Operating cycle: O - I - O - II - O
   74   75   76   77   78   79   80   81   82   83   84