Page 80 - Changeover switch
P. 80

80               ABB  TRANSFER AND CHANGE-OVER SWITCHES




          —
          Motorized change-over switches

          Technical data for OTM160...800_C




          Switch size                                       OT_160_  OT_200_  OT_250_  OT_315_  OT_400_  OT_630_  OT_800_
          Data according to IEC 60947-3
          Rated insulation voltage and rated   Pollution   V  1000  1000  1000   1000   1000   1000     1000
          operational voltage AC20/DC20  1)    degree 3  2)
          Dielectric strength                  50 Hz 1min.  kV  10  10    10     10     10     10       10
          Rated impulse withstand voltage  3)           kV   12    12     12     12     12     12       12
          Rated thermal current and rated    / ambient 40°C   In open air   A  160  200  250  315  400  630  800
          operational current AC20/DC20  / ambient 40°C   In enclosure  A  160  200  250  315  400  630  800
          ..with minimum conductor
          cross section                        Cu       mm²  70    95     120    185    240    2x185    2x240
          Rated operational current, AC-21A    up to 500 V  A  160  200   250    315    400    630      800
                                               690 V    A    160   200    250    315    400    630      800
          Rated operational current, AC-22A    up to 500 V  A  160  200   250    315    400    630      800
                                                690 V   A    160   200    250    315    400    630      800
          Rated operational current, AC-23A    up to 500 V  A  160  200   250    315    400    630      800
                                               690 V    A    160   200    250    315    400    630      800
          Rated operational current /          ≤ 110 V  A    160/2   200/2   250/2  315/1  1)    400/1  1)  630/1   800/1
          poles in series, DC-21A  6)          220 V    A    160/2   200/2   250/2  315/2  1)    400/2  1)  630/1   800/1
                                               440 V    A    160/3   200/3   230/3  315/3  360/3  630/2   720/2
                                               660 V    A    160/4   200/4   200/4  315/4  315/4   630/4  1)   630/4  1)
          Rated operational power, AC-23A  2)  230 V    kW   45    60     75     100    132    200      250
          The kW-ratings are accurate for      400 V    kW   90    110    140    160    220    355      450
          3-phase 1500 R.P.M. standard         415 V    kW   90    110    145    180    230    355      450
          asychronous motors
                                               500 V    kW   110   132    170    220    280    400      560
                                               690 V    kW   160   200    250    315    400    630      800
          Rated breaking capacity              up to 415 V  A  1 280  1 600  2 000  2 520  3 200  5 040  6 400
          in category AC-23                    500 V    A    1 280  1 600  2 000  2 520  3 200  5 040   6 400
                                               690 V    A    1 280  1 600  2 000  2 520  3 200  5 040   6 400
          Rated conditional short-circuit    Ip (r.m.s.) 80 kA, 415 V  îc (peak)  kA  40.5  40.5  40.5  59  59  83.5  83.5
          current I p (r.m.s.) and cut-off    Max. OFA_ fuse size   gG/aM  A/A  355/315  355/315  355/315   500/500   500/500  800/1 000  800/1 000
          current î c (peak) value. The cut-off
          current î c refers to values listed by   Ip (r.m.s.) 100 kA, 500 V  îc (peak)  kA  40.5  40.5  40.5  61.5  61.5  90  90
          fuse manufacturers (single phase    Max. OFA_ fuse size   gG/aM  A  315/315  315/315  315/315  500/450  500/450  800/800  800/800
          test acc. to IEC60269).
                                Ip (r.m.s.) 80 kA, 690 V  îc (peak)  kA  40.5  40.5  40.5  59  59  83.5  83.5
                                Max. OFA_ fuse size   gG/aM  A  355/315  355/315  355/315   500/500   500/500  800/1 000  800/1 000
          Rated short-time withstand current  Icw (r.m.s.)  690 V 0.15s  kA  15  15  15  31  31  38     38
                                               690 V 0.25s  kA  15  15    15     24     24     36       36
                                               690 V 1s  kA  8     8      8      15     15     20       20
          Rated short-time making capacity  3)  I cm (peak)  4)  690 V  kA  30  30  30  65  65  80      80
          Power loss / pole     With rated current      W    2.4   4      6.5    6.5    10     25       40
          Mechanical endurance  Number of oper. cycles  5)  Cycles  8 000  8 000  8 000  8 000  8 000  5 000  5 000
          Terminal bolt size    Metric thread diameter x   mm  M8x25  M8x25  M8x25  M10x30  M10x30  M12x40  M12x40
                                length
          Terminal tightening torque  Counter torque required  Nm  15-22  15-22  15-22  30-44  30-44  50-75  50-75
          Operating torque      3-pole change-over      Nm   7     7      7      16     16     27       27
                                switches
          Weight without accessories  3-pole switch     kg   5.7   5.7    5.7    10.2   10.2   17.5     17.5
                                4-pole switch           kg   6.4   6.4    6.4    11.4   11.4   20.4     20.4
          Data according to IEC 60947-6-1
          Class of equipment                                 PC    PC     PC     PC     PC     PC       PC
          Rated short-time withstand current  Icw (r.m.s.)  690 V 0.1s  kA  15  15  15  25  25  38      38
          Rated operational current, AC-31B    up to 415 V  A  160  200   250    315    400    650      720
          Rated operational current, AC-33B    up to 415 V  A  160  200   250    315    400    650      650
          1)  Utilization category B
          2)  These values are given for guidance and may vary acc. to the motor manufacturer
          3)  Short circuit duration > 50ms, without fuse protection
          4)  Max. distance from switch frame to nearest busbar / cable support 150 mm
          5)  Operating cycle: O - I - O - II - O
          6)  Further ratings on request
   75   76   77   78   79   80   81   82   83   84   85