5/62             ABB  MOTOR PROTECTION AND CONTROL

          —
          AS09..S ... AS16..S and

          ASL09..S ... ASL16..S  3-pole contactors - with spring terminals
          Technical data


          Built-in auxiliary contacts according to IEC
          Contactor types                AC operated AS09..S          AS12..S              AS16..S
                                         DC operated ASL09..S         ASL12..S             ASL16..S
          Rated operational voltage Ue max.      690 V
          Rated frequency (without derating)     50 / 60 Hz
          Conventional free air thermal current Ith - θ ≤ 40 °C  10 A
          Ie / Rated operational current AC-15
          acc. to IEC 60947-5-1       24-127 V 50/60 Hz 6 A
                                     220-240 V 50/60 Hz 4 A
                                     400-440 V 50/60 Hz 3 A
                                        500 V 50/60 Hz 2 A
                                        690 V 50/60 Hz 2 A
   05
          Making capacity AC-15                  10 x Ie AC-15 acc. to IEC 60947-5-1
          Breaking capacity AC-15                10 x Ie AC-15 acc. to IEC 60947-5-1
          Ie / Rated operational current DC-13
          acc. to IEC 60947-5-1             24 V DC 6 A / 144 W
                                            48 V DC 2.8 A / 134 W
                                            72 V DC 1 A / 72 W
                                           110 V DC 0.55 A / 60 W
                                           125 V DC 0.55 A / 69 W
                                           220 V DC 0.27 A / 60 W
                                           250 V DC 0.27 A / 68 W
          Short-circuit protection device gG type fuse  10 A
          Rated short-time withstand current Icw  for 1.0 s 100 A
                                            for 0.1 s 140 A
          Minimum switching capacity             12 V / 3 m
          with failure rate acc. to IEC 60947-5-4  10-7
          Non-overlapping time between N.O. and N.C. contacts  1.5 ms
          Power dissipation per pole at 6 A      0.1 W
          Max. electrical switching frequency  AC-15 1200 cycles/h
                                             DC-13 900 cycles/h
          Mechanically linked contacts           Built-in N.O. or N.C. auxiliary contacts and additional N.O. or N.C. auxiliary contacts (CA3 aux. contact blocks) are
          acc. to annex L of IEC 60947-5-1       mechanically linked contacts.
          Mirror contacts                        Built-in N.C. auxiliary contacts or additional N.C. auxiliary contacts (CA3 aux. contact blocks) are mirror contacts.
          acc. to annex F of IEC 60947-4-1

          Built-in auxiliary contacts according to UL / CSA
          Contactor types                AC operated AS09..S          AS12..S              AS16..S
                                         DC operated ASL09..S         ASL12..S             ASL16..S
          Max. operational voltage               600 V AC, 250 V DC
          Pilot duty                             A600, Q300
            AC thermal rated current             10 A
            AC maximum volt-ampere making        7200 VA
            AC maximum volt-ampere breaking      720 VA
            DC thermal rated current             2.5 A
            DC maximum volt-ampere making-breaking  69 VA