ABB  MOTOR PROTECTION AND CONTROL                                                5/59

          —
          AS09..S ... AS16..S and

          ASL09..S ... ASL16..S  3-pole contactors - with spring terminals
          Technical data


          Main pole - Utilization characteristics according to UL / NEMA / CSA
          Contactor types              AC operated AS09..S           AS12..S               AS16..S
                                       DC operated ASL09..S          ASL12..S              ASL16..S
          Standards                            UL 508, CSA C22.2 N°14
          Max. operational voltage             690 V
          NEMA size                            00                    00                    00
          NEMA continuous amp rating  Thermal current 9 A
          NEMA maximum horse power ratings 1-phase,   115 V AC 1/3 hp  1/3 hp              1/3 hp
          60 Hz                          230 V AC 1 hp               1 hp                  1 hp
          NEMA maximum horse power ratings 3-phase,   200 V AC 1-1/2 hp  1-1/2 hp          1-1/2 hp
          60 Hz                          230 V AC 1-1/2 hp           1-1/2 hp              1-1/2 hp
                                         460 V AC 2 hp               2 hp                  2 hp                       05
                                         575 V AC 2 hp               2 hp                  2 hp
          UL / CSA General use rating
            600 V AC                           12 A                  12 A                  15.2 A
            With conductor cross-sectional area  AWG 14              AWG 14                AWG 12
          UL / CSA maximum 1-phase motor rating
            Full load current            120 V AC 7.2 A              9.8 A                 13.8 A
                                         240 V AC 8 A                10 A                  12 A
            Horse power rating           120 V AC 1/3 hp             1/2 hp                3/4 hp
                                         240 V AC 1 hp               1-1/2 hp              2 hp
          UL / CSA maximum 3-phase motor rating
            Full load current (1)     200-208 V AC 7.8 A             7.8 A                 11 A
                                      220-240 V AC 6.8 A             9.6 A                 15.2 A
                                      440-480 V AC 7.6 A             11 A                  14 A
                                      550-600 V AC 9 A               11 A                  11 A
            Horse power rating (1)    200-208 V AC 2 hp              2 hp                  3 hp
                                      220-240 V AC 2 hp              3 hp                  5 hp
                                      440-480 V AC 5 hp              7-1/2 hp              10 hp
                                      550-600 V AC 7-1/2 hp          10 hp                 10 hp
          Short-circuit protection device for contactors
          without thermal overload relay - Motor protection excluded
            Fuse rating                        40 A                  50 A                  60 A
            Fuse type, 600 V                   J
          Max. electrical switching frequency
            For general use                    600 cycles/h
            For motor use                      1200 cycles/h
          (1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".

          General technical data
          Contactor types              AC operated AS09..S          AS12..S              AS16..S
                                       DC operated ASL09..S         ASL12..S             ASL16..S
          Rated insulation voltage Ui
            acc. to IEC 60947-4-1              690 V
            acc. to UL / CSA                   600 V
          Rated impulse withstand voltage Uimp.  6 kV
          Pollution degree                     3
          Ambient air temperature close to contactor
            Operation                          -40...+70 °C
            Storage                            -60...+80 °C
          Climatic withstand                   Category B according to IEC 60947-1 Annex Q
          Maximum operating altitude (without derating)  3000 m
          Mechanical durability
            Number of operating cycles         10 millions operating cycles
            Max. switching frequency           3600 cycles/h
          Shock withstand                      1/2 sinusoidal shock for 11 ms: no change in contact position, closed or open position
          acc. to IEC 60068-2-27 and EN 60068-2-27  Shock direction AS contactors - AC operated  ASL contactors - DC operated
          Mounting position 1                A 20 g                           20 g closed position / 10 g open position
                        C1
                                            B1 10 g closed position / 5 g open position  15 g closed position / 5 g open position
          A      A  B1      B2              B2 15 g                           10 g
                                            C1 20 g closed position / 9 g open position  15 g closed position / 8 g open position
                        C2                  C2 20 g closed position / 14 g open position  14 g closed position / 8 g open position
          Vibration withstand  acc. to IEC 60068-2-6  5...300 Hz / 3 g closed position / 2 g open position